STIEBEL ELTRON LWZ 130 Bedienung Und Installation Seite 58

Vorschau ausblenden Andere Handbücher für LWZ 130:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
INSTALLATION
Settings
12.1.4 "Settings" menu
Settings
View
C]'
General
C]C]• Language
C]O•
Contrast
C]C]• Brightness
C]CJ• Touchsensitivity
CICI•
Touch
boost
C]C]• Prog. unit software
Air flow
rate
C]C]• Flowrate.stageO
CIC]• Flow rate, stage I
Flow rate, stage 2
C]C]• Flow rate. stage 3
C]a• Supply air flow rate offset
Favourites
C]' Humidity prot.
C]CJ• Enable humidity control
C]C]• Humidity prot. interval
C]C]• Humidity threshold
C]Cj• Humidity capture delav
C]•
Intensive
ventilation
C]Lj•
Intens.
vent.
time
C]• Heat recovery bypass
Setroomtemperature
C]Cj• Operating mode heat recovery bypass
C]C]• Temperature to enable heat recovery
bypass
C]CJZ Temperatureto block heat recovery
bypass
CID' Hysteresisfor heat recovery bypass
C]C]• Temp. differential for heat recovery
bypass
C]a•
Window
contact mode (A2)
(depending on unit)
C]CJ• Cooling/heating. heat recovery bypass
Frost protection
C]CJ• Frost protection temperature
C]C]• Vernp. t o enable frost protection (A2)
C]CJ• Enable preheating
58 | LWZ 130 | I-WZ 130 Enthalpie
Value
Code for qualified contractor
Day
Hour:Minute
Deutsch
English
Francms
Nederlands
Italiano
Pols
I
Cesky
Magvar
Slovensko
S ovens
1 - 10
1 - 10
rnj/h
m3/h
rn3/h
rn3/h
rn3/h
Bypass status
Filter
runtime
Device
software
version
Deviceso tware patch
Mobile
device
serial
no.
Onlyfor qualified contractors
Off
On
h
min
min
Disabled
Bypass/window contact
Outdoorair routingautomatic
Extract air routing autom.
Without
window
contact
With
window
contact
Cooling/heating
Cooling
Heating
Onlyfor qualified contractors
Off
On
I LWZ 130 E-W
Condensateprevention (A2)
C]O•
Enable condensate prevention
CJCj• Offset condensateprevention
DE
Enable
fan
Ventilation
unit
CJCJ•
Device software
version
C]Cj• Devicesoftware patch
C]C]•
Mobile
device
serial
no.
OO•
Devicetype
Settings
C]
View
Effect
Standard (AO)
The only parameters displayed are those that have been re-
leased for the appliance user and can therefore be accessed
without
a code.
Service (A1)
Parametersfor qualified contractors: Code"I OOC"
Expert (A2)
Parametersfor service department.
To accessactual values and parameters which are reserved
for qualified contractors, enter the code "1 0 0 0" for "View".
Press "0K".
"Service" is shown on the display, when this is entered correctly.
If you switch to the actual values or parameters, you see the en-
abled parameters.
Notice
After entering the code, switch to the menu by pressing
the "MENU"button. If you first switch to the home screen,
the parameter block is reactivated.
D • Air flow
rate
Supply air flow rate offset
Usethis parameter to adjust the supply air flow rate during com-
missioning. The offset refers to standard ventilation and is con-
verted internally as a percentage for the other fan stages.
Example
Nominal flow rate (stage 2)
Offset
Stage
Set flow
Off-
Set flow
rate
set
rate
+
offset
50
1
130
= 225 225/180
2
180
45 180+45
3
235
Off
on
Off
On
rn3/h
rn3/h
Offset
fac-
internal
set flow
rate
= set
flow
tor
rate
* offset
factor
50*1.25
= 62
130*1.25
= 162
= 1.25 180*1.25
= 225
235*1.25
= 294
www.stiebel-eltron.com