INSTALLATION
Installation
10.5.2 Installing the programming unit
Route a 4-core
bus cable
from
mounting position of the programming unit. Use a screened
electronic
cable
such as LiYCY 2x2x0.8
cable parallel to a three-phase cable.
The BUScable must protrude 20 to 30 cm out of the wall to allow
installation.
Remove programming unit from the wall mounted enclosure
Releasethe locking tab found in the opening on the under-
side of the wall mounted enclosure. Pressthe locking tab
with
a screwdriver.
Installation
with
a flush
box
For securing to a wall we recommend using a flush box,which can
hold the part of the bus cable protruding from the wall.
Make sure that the screws supporting the flush box are ar-
ranged either vertically or horizontally opposite one another.
Route the bus cable through the aperture in the wall mount-
ed enclosure
from
the back.
Installation
without
a flush
box
To secure the wall mounted
(Ø 5 mm).
When routing the BUScable, be careful not to damage the
cable when drilling the fixing holes.
In the area around the cable entry (behind the wall mounted en-
closure), a reservoir needs to be made to hold 20 to 30 cm of data
cable.
Break
out one of the knock-outs
enclosure.
54 | LWZ 130 | l-wz 130 Enthalpie
the ventilation
unit to the
mm2. Do not route
enclosure,
drill four holes
0
in the wall
mounted
I LWZ 130 E-W
Route the bus cable through the aperture from the back.
Installing the wall mounted enclosure
the
I
Flush
box
Secure
the wall
mounted
wall using the screws provided.
10.6
Electrical
connection
WARNING
Electrocution
Carry out all electrical connection and installation
in accordance with national and regional regulations.
WARNING
Electrocution
The connection to the power supply must be in the form
of a permanent connection. Ensurethe appliance can be
separated from the power supply by an isolator that dis-
connects all poles with at least 3 mm contact separation.
WARNING
Electrocution
Before any work on the appliance, isolate the connecting
cables in the control panel.
WARNING
Electrocution
Do not install the appliance if it is damaged and there is
a risk that live components could be touched.
Checkthe appliance for external damage.
Property damage
Observe the fuse protection required for the appliance
(see chapter "Specification / Data table").
Notice
For the power cable, connections and connecting cables
to external control equipment, observe chapter "Electrical
connection" and the wiring diagram in chapter "Speci-
fication".
Takethe power consumption of the preheating coil into
consideration.
c
enclosure
to the flush
box or to the