INSTALLATION
Installation
Connect
a condensate
hose to the condensate
condensate pump and route it into a drain. In order for the
condensate pump not to run dry, the condensate hose behind
the pump must not route directly downwards.
Connectthe power supply of the condensate pump.
Colour
WH
10.3 LWZ 130 E-W: Pipe bend with condensate drain
If the applia nceis mounted vertically on the wall, the "extract air"
connection must be replaced with a pipe bend with condensate
drain.
To remove the "extract air" connection, undo the screws.
Removethe "extract air" connection and its gasket.
I O-ring
2 Pipe bend with condensate drain
Checkthat the preassembled O-ring is seated correctly to en-
sure that it seals the pipe bend to the appliance.
Attach the pipe bend to the extract air opening on the appli-
ance with
screws.
52 | I-WZ 130 ll-wz 130 Enthalpie
outlet
of the
Ground
Neutral
Phase
1
2
I LWZ 130 E-W
Connecting the condensate drain hose
Property damage
The drain pipe may only contain one siphon. The con-
densate must be able to drain freely downstream of the
siphon. The condensatemust drain away via the domestic
sewer system. The pipes must not rise in the domestic
sewer system downstream of the siphon. The condensate
drain
must
be free from
Notice
1
To ensure the unit is airtight, there may be no inter-
ruption in the condensate drain between the unit and
the trap. Use the supplied condensate drain hose and
mounting bend.
Before connecting the condensate drain hose to the appli-
ance, pour water into the trap.
Use the mounting bend included in the standard delivery to
install the condensate drain hose in such a way as to create a
siphon with a water trap height of at least 80 mm.
Secure
the condensate
drain
the pipe bend using the hose clip provided.
10.4
Air ducts
Property damage
Never link cooker hoods to the ventilation system.
Property damage
During installation, ensure that no metal swarf enters
the pipework. However, should this occur, remove this
debris, otherwise the fans may be damaged.
Install the air ducts using materials that can be obtained from us
or with commercially available folded spiral-seam tubes.
the risk of frost.
090
3
hose to the condensate
drain
www.stiebel-eltron.com