Herunterladen Inhalt Inhalt Diese Seite drucken

Activation Condition For The Relays; Control Functions - Honeywell 8010 Bedienungs- Und Installationsanleitung

Löschmittel-ansteuereinrichtung
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

17.3.3 Activation condition for the relays

The relays activation (AE) relates to the assigned operating mode or, respectively for relays 1 to 8
relating to the selected mode >monitoring< or >dry contact<.

17.3.3.1 Control functions

In case of an event the relay is activated relating to the selected control function in the programming software.
Pre-alarm (VA)
The assigned relay (AE) is activated for the duration of the pre-alarm time.
Evacuation alarm (RA)
The assigned relay (AE) is activated for the duration of the evacuation alarm time.
Area valve (BV)
The assigned relay (AE) is activated at the start of the evacuation alarm until all alarms are reset.
In case of pre-controlled dry systems the alarm valve of the associated alarm valve control is activated.
Tank valve (TV)
The assigned relay (AE) of the tank valve is activated for the duration of the release and extra releasing time.
Emergency Stop valve (NSV)
The assigned relay (AE) for activating the emergency stop valve (NSV) can be activated at the start of
release for the duration of the actual release time.
Pre-control valve (VV)
The assigned relay (AE) for activating the pre-control valve (VV) is activated at the start of the release or
extra releasing time and remains active until the end of the respective extra releasing time.
Control valve (SV)
The assigned relay (AE) for activating the control valve (SV) is activated at the start of the evacuation time.
Pilot valve (PV)
This output is used in extinguishing systems with separate activation for the main and spare tanks.
The assigned relay (AE) for activating the pilot valve (PV) is activated if the spare detector zone (MG7) is not
active at the start of extinguishing. Its time behaviour is the same as the tank valve (TV). If the spare detector
zone is active, this output remains inactive.
Spare valve (RV)
This output is used in extinguishing systems with separate activation for the main and spare tanks.
The assigned relay (AE) for activating the spare valve (RV) is activated if the spare detector zone (MG7) is
not active at the start of extinguishing. Its time behaviour is the same as the tank valve (TV). Under normal
conditions, with an active spare zone, this output remains inactive.
Spraying nozzle (only for AquaSafe)
The
relay
activation
Switch-on/off times (spray intervals) to activate spray release systems can be implemented with this relay
output.
FB 798352 / 11.07
(AE)
relates
to
the
Extinguishing Control Computer 8010 - Series 2
programmed
data
of
the
AquaSafe
functionality.
99

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis