Herunterladen Inhalt Inhalt Diese Seite drucken

Third-Party Detectors - Honeywell 8010 Bedienungs- Und Installationsanleitung

Löschmittel-ansteuereinrichtung
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Extinguishing Control Computer 8010 - Series 2

20.3 Third-party detectors

Third-party detectors, e.g. the line-type smoke detector Fireray 50RV (Part No. 761315) or 100RV
(Part No. 761316) are connected to the Extinguishing panel 8010 series 2 via the Reset module
(Part No. 781332 / 781333).
Fit jumpers
6
5
4
3
2
1
Jumper X3, X5, X7, X8 fitted!
Jumper X4, X6 removed!
Connect cable shielding!
Observe wiring sequence!
For detailed informations and third-party detector wirings refer to the technical manual of the
Reset module.
112
X5
X6
X7
X8
K1
X3
X4
Reset module
X2
black
5
red
4
blue
2
white
7
yellow
3
6
green
6
5
4
3
2
1
X1
R
A LA R M
1K
10K
R
E ND
Plug w ith cable
(lengh t appro x. 50cm )
Extinguishing Control Computer
standard detector zone
Detector zone input
Gn -
Gn +
Extinguishing Control Computer
external power supply or
DC/DC converter
(Min. 1A switch current)
0V
+24V
FB 798352 / 11.07