Honeywell 8010 Bedienungs- Und Installationsanleitung Seite 95

Löschmittel-ansteuereinrichtung
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

F5, F6, F8, F9,
F11, F12, F13, F16
F2, F3, F4
F1, F7
F10
F14, F15
J1 to J4, J6,
J8 to J18
J5
J7
Poti
Relay 1 to 8
Relay. 9 to Rel. 11
Relay 12 + 13
X47
X57
X11 / UB
EXT
FB 798352 / 11.07
Fuses - low-voltage relays no. 1 to 8
Relay 1:
F16,
Relay 2:
F13,
Relay 3:
F12,
Relay 4:
F11,
Relay 5:
F9,
Relay 6:
F8,
Relay 7:
F6,
Relay 8:
F5,
Fuses - low-voltage relays No. 9, 10 and 11
Relay 9:
F2,
Relay 10:
F3,
Relay 11:
F4,
Fuses - Mains voltage relays
Relay 12:
F1,
Relay 13:
F7,
Fuses of the supply voltage for external units, UBext, T 3,15 A / 250 V
Fuses of the emergency power supply (rechargeable battery)
Battery 1:
F14,
Battery 2:
F15,
Jumpers to program the operating mode for relay no. 1 to 8,
(monitoring or dry contact).
Factory setting
monitoring
Jumper to set the CPU-failure-mode function for relay 11
Emergency operation - fault
Inactive
deactivated (factory setting)
Active
activated
Jumper to set the CPU-failure-mode function for relay 10
>Emergency operation - fire <
Inactive
deactivated (factory setting)
Active
activated
Potentiometer for adjusting the battery charging voltage 27.5 V DC (@ 25°C)
Low-voltage relays, monitored or dry contact
Low-voltage relays, dry contact
Mains voltage relays, dry contact
Terminal for the ribbon cable to the zone board
Plug for PE connection to the housings rear wall
Terminals for the Supply voltage for external units +24 V DC / GND
Extinguishing Control Computer 8010 - Series 2
T2 A / 250 V
T2 A / 250 V
T2 A / 250 V
T2 A / 250 V
T2 A / 250 V
T2 A / 250 V
T2 A / 250 V
T2 A / 250 V
T2 A / 250 V
T2 A / 250 V
T2 A / 250 V
T 3,15 A / 250 V
T 3,15 A / 250 V
T 3,15 A / 250 V
T 3,15 A / 250 V
contact rating
30 V DC / 2 A
contact rating
230 V AC / 2 A
95