The terminal assignment and wiring illustrated in these installation instructions refer exclusively to the facilities of the
operating system software for the Federal Republic of Germany [D].
Operation of the Extinguishing Control Computer 8010 is governed by the national version of the operating system
software used and the country version programmed in the customer data.
A complete system check must be carried out after commissioning and for each modification of
the customer data programming!

14.1 Installation information

The Extinguishing Control Computer 8010 must be installed in a dry, clean room with controlled access and
appropriate lighting. The environmental conditions must comply with DIN EN 60721-3-3, class 3k5.
The device must be mounted on a flat surface using appropriate hardware (screws and dowels). Avoid
mechanical stressing. It may only be commissioned after correct mounting on a wall or other mounting
surface of sufficient strength to support the weight of the unit.
Avoid strong electric or magnetic fields as well as mechanical influences. This applies especially to the
presence of fluorescent lighting or energy cabling in the close vicinity of the device, its components and the
associated cabling. Do not mount on vibrating, unstable surfaces such as light partitioning walls.
Do not install the system in places where adverse conditions prevail. Parts and components of the system
may only be installed in or led through locations which allow compliance with DIN VDE 0800.
Connect the FE (functional earth) and PE (protective earth) terminals of the panel's cabinet with the PE rail
of the power distribution panel from which the fire alarm system will be powered.
Control panels and visual indicators mounted on a wall should be installed at a height of 800 to 1800 mm
above the floor.
The fire alarm system is not suited for connection to IT power supply systems.
Danger – Electrical shock !
Remove all power from the panel before carrying out any installation work!
ESD protection
While handling electronic assemblies, the necessary precautions against electrostatic discharge
must be taken.
Protective and functional earth
The PE conductor must be connected to the corresponding terminal at the mains supply. Connect
the FE terminal of the panel's cabinet with the PE rail of the power distributor panel from which the
fire alarm system will be powered.
FB 798352 / 11.07
Extinguishing Control Computer 8010 - Series 2
79