Branch Circuit Protection
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes (US) or Canadian Electrical Code, Part 1 (CA).
WARNING - The opening of the branch-circuit protective device may be an indication
that a fault current has been interrupted. To reduce the risk of fire or electric shock,
current-carrying parts and other components of the controller should be examined and
replaced if damaged. If burnout of the current element of an overload relay occurs, the
complete overload relay must be replaced.
ATTENTION - LE DÉCLENCHEMENT DU DISPOSITIF DE PROTECTION DU CIR-
CUIT DE DÉRIVATION PEUT ÊTRE DÛ À UNE COUPURE QUI RÉSULTE D'UN
COURANT DE DÉFAUT. POUR LIMITER LE RISQUE D'INCENDIE OU DE CHOC
ÉLECTRIQUE, EXAMINER LES PIÈCES PORTEUSES DE COURANT ET LES AU-
TRES ÉLÉMENTS DU CONTRÔLEUR ET LES REMPLACER S'ILS SONT ENDOM-
MAGÉS. EN CAS DE GRILLAGE DE L'ÉLÉMENT TRAVERSÉ PAR LE COURANT
DANS UN RELAIS DE SURCHARGE, LE RELAIS TOUT ENTIER DOIT ÊTRE REM-
PLACÉ.
For maximum branch circuit protection see table below.
Series
MOVIFIT
Motor Overload Protection
MOVIFIT
150 % of the rated current.
Device and Line Protection
MOVIFIT
protection and line protection.
Ambient Temperature
MOVIFIT
ted output current. To determine the output current rating at higher than 40°C, the out-
put current should be derated 3.0 % per °C between 40°C and 60°C.
ABOX-EBOX Combination
For UL-compliant installation, only the EBOX specified on the ABOX nameplate may
be mounted to the ABOX. The UL certification refers only to the ABOX/EBOX combi-
nation stated on the nameplate.
HINWEIS
The UL certification only applies for operation on voltage supply systems with volta-
ges to ground of max. 300  V. UL approval does not apply for operation on voltage
supply systems with a non-grounded star point (IT systems).
Wiring Diagrams
For wiring diagrams, please refer to the English operating manual "MOVIFIT
SC" (see www.sew‑eurodrive.com).
non-semiconductor fuses
®
-SC
25 A / 600 V
®
-SC is provided with motor overload protection with a trip current adjusted to
®
-SC: Units in connection with ABOX MTA....-M12-.. are provided with device
®
-SC is suitable for an ambient temperature of 40 °C, max. 60 °C with dera-
Elektrische Installation
Installationsvorschriften (alle Ausführungen)
inverse time circuit breaker
Korrektur – MOVIFIT
3
®
-
7
®
-SC