Connection terminals
Tightening torque
max. 0.4 Nm
Wire cross section max. 2.5 mm
Earthing connection max. 4 mm
7.3 Pressure Connection as for 1.3
62
7. Pressure Monitors in Ex-d Version Ex-DWR..., Ex-DGM...
7.4 Setting of the Switching Point
2
The switching point can be set within the
2
range given in the datasheet by using a
screwdriver on the setting spindle.
Additionally, you should remove the
terminal board casing (with 4 hexagon
screws M 4). The affixing screw on the
front end (above the scale) must be
removed and should be reattached after
setting the switching point.
Turning the setting spindle clockwise
results in a lower switching point, turning
anticlockwise results in a higher switching
point.
The scale can be used as a guide; for
more exact settings you should use a
manometer.
MU2B-0264GE51 R0220G