Herunterladen Diese Seite drucken

Honeywell Fema DWR Serie Montage- Und Bedienungsanleitung Seite 55

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3. Pressure Limiters with Mechanical Interlock of Switching State
3. Pressure Limiters with
Mechanical Interlock of Switching
State
(applies for DWR and roughly for
DGM)
Fig. 10. Mechanical interlock
Instead of the microswitch with automatic
reset, a "bi-stable" microswitch is installed
in the limiters.
When the pressure reaches the value
preset on the scale, the microswitch
switches over and remains in this
position. The catch can be released by
MU2B-0264GE51 R0220G
pressing in the unlocking button (marked
on the scale side of the switching device
by a red dot). The limiter cannot be
unlocked until the pressure has
decreased by a certain amount or, in
case of interlocking at the lower switching
point, is increased again.
Depending on the version, the interlock
can be effective for a rising (DWR...-205 /
-305) or a falling value (DWR...-206 / -
306).
3.1 Technical Data as for 1.1
55