1.4 Setting the Switching Pressure
Fig. 4. Setting the switching pressure
48
1. Basic Equipment of the Pressure Monitors / Pressure Limiters
CAUTION:
SWITCH OFF VOLTAGE!
The switching pressure is set using the
setting spindle. Before setting, loosen the
setscrew located above the scale by
approx. 2 turns and tighten it again after
setting.
The scale value corresponds to the
switching point (for rising pressure).
The reset point is lower by the value of
the switching differential.
The scale is used for an approximate
value; a pressure gauge is required for an
accurate setting.
On terminal connection housings, the
setting screw is accessible after removing
the cover.