4. Pressure Limiters with Gold-Plated Contact DWR...-213 / -313 / 363, DGM...-213 / -313 / 363
3.3 Pressure Connection as for 1.3
3.4 Setting as for 1.4
NOTE:
In the case of maximum pressure limiters
(...-205 / -305), the scale value corresponds
to the upper switching point, for minimum
pressure limiters (...-206 / -306) to the lower
switching point.
MU2B-0264GE51 R0220G
4. Pressure Limiters with Gold-
Plated Contact DWR...-213 / -313 /
363, DGM...-213 / -313 / 363
Gold-plated contacts are used exclusively
in the low-voltage range in order to keep
the transfer resistance at the contacts
low.
4.1 Technical Data as for 1.1
Switching capacity max. 24 V DC
max. 100 mA
min. 5 V DC
min. 2 mA
At higher voltages and currents, the gold
layer on the contacts will be damaged.
All other data correspond to the basic
equipment.
57