1. Basic Equipment of the Pressure Monitors / Pressure Limiters
1.3 Pressure Connection
Installation
Directly on the pipeline (pressure gauge
connection G ½" or G ¼" internal thread)
or (on a flat surface) with 2 screws Ø 4
mm. Tighten the device only at the
hexagon located closest to the pressure
connection. Never tighten device at
housing or other area of sensor parts.
Never use housing or plug as a lever arm.
MU2B-0264GE51 R0220G
External thread
Internal thread
Fig. 3. Pressure switch
External thread G ½"
(Pressure gauge connection)
When using flat seals, turn in the center-
ing screw (depth A approx. 0.3 – 0.5 mm)
Internal thread G ¼"
In gas applications, internal thread is per-
missible only up to pressures of 4 bar.
Use flat gasket ring for pressure > 4 bar.