Herunterladen Diese Seite drucken

BWT Bolero RF Serie Einbau- Und Bedienungsanleitung Seite 38

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

EN
A
A
38
13
Maintenance instructions
13.1
Maintenance Bolero
5
RF 3/4" – 1 1/4"
Drinking water is intended for human consumption.
Therefore, it is important to maintain hygiene when
performing work.
The BWT after-sales service staff or an installer
D
authorised by BWT must carry out the following
maintenance work regularly.
Replacement of wearing parts
C
Sealing components (A)
Filter element (B)
Transparent cylinder (C)
O-Ring for bayonet (D)
Replacement of wearing parts 3/4
B
Sealing components set
Filter element
Transparent cylinder
O-Ring for bayonet
Close the stop valves up and downstream of the
filter and place a collecting basin underneath if
necessary.
Relieve pressure from the filter (open rotary knob
5 counterclockwise).
Unscrew the transparent cylinder (C) by hand and
C
pull vertically downwards.
Pull filter element (B) downwards.
Replace seals (A).
Lightly grease all seals before installation.
Flush the filter element with water and check filter
cloth for any damage or replace if necessary. Attach
the filter element.
Screw transparent cylinder into the top section by
hand.
Open the stop valves up and downstream from
the unit, bleed the piping with the closest water
tap downstream from the unit, and drain the water.
Check all connections for leaks (visual check).
Carry out backwash.
every 4 years
every 6 years
every 16 years
every 16 years
"
"
- 1 1/4
Order-No.
1-902345
1-902393
1-902356
1-181548

Werbung

loading