9
Operator's responsibilities
You have purchased a durable and service-friendly
product. However, this also entails obligations. For
a perfect function you must ensure:
● Intended operation.
● Regular inspections and service work.
Changes in the water quality may have to be made
in the settings. Prerequisites for the function and
safety of the product are inspections, regular in-
spections (every 2 months) by the operator and a
half-yearly (every 6 months) routine maintenance
(EN 806-5) of the entire drinking water installation.
A further prerequisite for function and warranty is
the replacement of wear parts at the prescribed
intervals.
9.3
Inspection
(according to EN 806-5 by the operator)
Inspection activity
Check contamination of
the filter element
Leak test, visual ins-
pection
Function check / display
of the control
Check the fixation of the
waste water system
Backwash process
check
34
Interval
WITHOUT active BWT-
every 2 months
every 2 months
every 2 months
every 2 months
every 2 months
9.1
Intended operation
The intended operation of the product includes
commissioning, operation, decommissioning and,
if necessary, recommissioning. Proper operation
of the product and the drinking water installation
requires regular checks, servicing and operation in
compliance with the operating conditions used for
planning and installation.
9.2
Controls
(by the operator)
BWT recommends that the operator regularly car-
ries out and logs the following checks:
● Water pressure: If the pressure conditions
change, the product settings may also have to
be changed.
● Operating condition of the product (soiling).
● Checks whether (error) messages have been
issued.
● Tightness.
Note for products
DES registration
Required
Required
Required
Required
Required
Note for products
WITH active BWT-
DES registration
Required
Required
Not required
Required
Required

Werbung