Informations for starting

Carry out following sight and performance checks for switching-on the smoke and heat vent
control panel.
All necessary moving loads connected?
Smoke vent components are line-monitored.
A malfunction is connected as alarm in delivery condition of
control panel. The smoke vent opens self-acting and can be
reset under special conditions only.
10kΩ resistor in
10kΩ resistor in fire
in junction box?
Connect mains.
LED mains lightens?
Connect battery
Performance check alarm/reset and ventilation
Smoke vent flap opens
30/36
RZN 4416-M
All cables
connected?
yes
yes
Factory set?
(DIP switch)
yes
smoke vent
button?
yes
detector?
yes
End module
2x47kΩ
yes
yes
lines. Control l
ightens?
yes
yes
and closes?
Partial or incomplete connection of
no
components can cause malfunction.
Check following connections: mains 230 V,
drives, smoke vent buttons, when necessary
fire detectors and vent buttons.
See wiring an connection plans pages 27-29.
no
Delivery condition of DIP switch see
pages 24-25.
Resistor must be cramped in electric last
button on terminal 3/8 (RT 45).
no
See connection plan pages 28.
Resistor must be cramped in last or only fire
detector on terminal 3 and 5 (SD-O/FD-T).
Resistor remains in control panel between
no
terminal RM "R" and "–", when no fire
detector is connected.
See connection plan page29.
no
End module on last or only drive in junction
box on wire 5 orange, 6 black, 7 black.
See connection plan page 27.
no
Check line safety fuse in distribution box and
fuse mains in control panel.
Mains still not available or line switch on "0"
no
or one of fuses faulty.
no
Possibly change poles in drive.