RDC104-4 (Switch2, IEC 62955)
Auslösefehlerstrom I
.............................................................DC 6 mA
Δdc2
Ansprechtoleranz I
....................................................> 0,5...1 x I
Δdc2
Wiederzuschaltwert I
..........................................................< 2,5 mA
Δdc2
Ansprecheigenzeit t
ae
DC 6 mA ...................................................................................< 480 ms
DC 12 mA .................................................................................< 240 ms
DC 30 mA .................................................................................< 120 ms
DC 60 mA ...................................................................................< 70 ms
DC 200 mA .................................................................................< 30 ms
DC 300 mA .................................................................................< 30 ms
Ausgänge Switch1, Switch2, Error
Ausführung ...........................................................Open Collector (NPN)
Schaltvermögen ........................................................... DC 40 V/20 mA*
Meldezeiten bei Modul- und Hardwarefehler
Error .............................................................................................≤ 1,5 s
Switch1 ........................................................................................≤ 1,5 s
Switch2 ........................................................................................≤ 1,5 s
PWM-Ausgang
Ausführung .............................................................................. PushPull
HIGH-Pegel ........................................................................ 3,1...3,5 V*
LOW-Pegel ............................................................................0...0,5 V*
PWM-Frequenz ......................................................................... 8000 Hz
Skalierung
RDC104-4 ................................................... 0...100 % = DC 0...30 mA
Maximale Strombelastbarkeit ......................................................10 mA
* Der Überspannungsschutz muss kundenseitig sichergestellt werden.
Steuereingang (TEST)
Ausführung .....................................................LOW: aktivierter Zustand
.................................................................... HIGH: deaktivierter Zustand
Schaltschwellen ........................................................ HIGH: 3,1... 5,5 V
.......................................................................................LOW: 0... 0,6 V
EMV (IEC 62955)
Einschränkungen ESD: Das Gerät muss in ein den genannten Normen
entsprechendes Gehäuse eingebaut werden.
Einschränkungen leitungsgebundene Störungen:
Maximale Anschlusslänge: .........................................................100 mm
ESD-Festigkeit nach Human Body Model JESD22-A114 ............... .....
............................................................................................ ±2 kV (Luft)
...................................................................................... ±2 kV (Kontakt)
Arbeitstemperatur ............................................................. –30...80 °C
Lagertemperatur ................................................................ –40...85 °C
RDC104-4 (Switch2, IEC 62955)
Rated residual operating current I
Response tolerance I
Δdc2
Δdc2
Restart value I
.....................................................................< 2.5 mA
Δdc2
Operating time t
ae
DC 6 mA ...................................................................................< 480 ms
DC 12 mA .................................................................................< 240 ms
DC 30 mA .................................................................................< 120 ms
DC 60 mA ...................................................................................< 70 ms
DC 200 mA .................................................................................< 30 ms
DC 300 mA .................................................................................< 30 ms
Outputs Switch1, Switch2, Error
Type ......................................................................Open Collector (NPN)
Switching capacity ....................................................... DC 40 V/20 mA*
Signalling times in the event of module and hardware errors
Error .............................................................................................≤ 1.5 s
Switch1 ........................................................................................≤ 1.5 s
Switch2 ........................................................................................≤ 1.5 s
PMW output
Type ......................................................................................... PushPull
HIGH level .......................................................................... 3.1...3.5 V*
LOW level ..............................................................................0...0.5 V*
PWM frequency ......................................................................... 8000 Hz
Scaling
RDC104-4 ................................................... 0...100 % = DC 0...30 mA
Maximum current-carrying ability ...............................................10 mA
* The overvoltage protection must be ensured by the customer.
Control input (TEST)
Type ..................................................................... LOW: activated state
...........................................................................HIGH: deactivated state
Switching thresholds ................................................ HIGH: 3.1... 5.5 V
.......................................................................................LOW: 0... 0.6 V
EMV (IEC 62955)
ESD restrictions: The device must be mounted in an enclosure that
complies with the mentioned standards.
Restrictions line-conducted interferences:
Maximum connection length: ....................................................100 mm
ESD immunity acc. to Human Body Model JESD22-A114 ............... ...
...............................................................................................±2 kV (air)
.......................................................................................±2 kV (contact)
Operating temperature ...................................................... –30...80 °C
Storage temperature .......................................................... –40...85 °C