Herunterladen Inhalt Inhalt Diese Seite drucken

Parameter Manager - Balluff BES M12EG1-L01C80F-S04G-L04 Konfigurationsanleitung

Vorschau ausblenden Andere Handbücher für BES M12EG1-L01C80F-S04G-L04:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BES M12EH1-L01C40B-S04G-L04 / BES M12EG1-L01C80F-S04G-L04 /
BES M18EH1-L01C80B-S04G-L04 / BES M18EH1-L01C12F-S04G-L04
Inductive sensors
6
System Functions (continued)
6.9

Parameter Manager

6.9.1
Description
The parameter manager is responsible for the saving of
parameters in the permanent memory of the device. On
startup, all stored parameters are read from permanent
memory; if parameters are changed, the data is stored
within the permanent memory by the parameter manager.
All data is protected with a CRC32 checksum. In the event
of damaged memory, the parameter manager outputs the
Parameters not consistent event.
6.9.2
Events
Event Code
Event Type
0x8D24 (36132)
Warning
0x8D25 (36133)
Error
Tab. 6-29: Parameter manager – Events
www.balluff.com
Description
Parameter write error – for information purposes
only.
Parameters not consistent – basic settings are
used, service required. Parameterization
processes and resets can no longer be
performed
Device Status
0 – Device is operating properly.
4 – Failure