Primary Device Functions (continued)
Switchpoint Mode
The AdSS profile only supports one switching
point (setpoint). Accordingly, only the Single Point
Mode is available in this profile.
Single Point Mode
In Single Point Mode, only one switching point (setpoint) is
defined.
Switching behavior:
Measurement value ≥ switching point: output active
Measurement value ≤ switching point minus a defined
hysteresis: output inactive
Low
SP1-Hys
SP1
Fig. 4-3:
Single-Point Mode
Two-Point Mode
In Two-Point Mode, two switching points (setpoints) are
defined.
Switching behavior:
Measurement value ≥ switching point 1: output active
Measurement value ≤ switching point 2: output inactive
Low
SP2
SP1
Fig. 4-4:
Two-Point Mode
www.balluff.com
High
Measurement value
High
Measurement value
Window Mode
In Window Mode, two switching points (setpoints) are
defined.
Switching behavior:
If the output is inactive and the measurement value is
greater than or equal to switching point 2 + 50% of the
set hysteresis or the measurement value is less than or
equal to switching point 1 – 50% of the set hysteresis,
the output switches to active.
If the output is active and the measurement value is
less than or equal to switching point 2 – 50% of the set
hysteresis or the measurement value is greater than or
equal to switching point 1 + 50% of the set hysteresis,
the output switches to inactive.
Hyst.
Low
SP2
Fig. 4-5:
Window Mode
Teach Process
For a successful teach-in as well to directly set a setpoint,
the following conditions must be met:
The setpoint that is to be taught must be in the validity
range of the measurement value signal.
Additionally in Two-Point and Window Mode:
Setpoint 1 must be greater than setpoint 2.
The distance between the setpoints must be greater
than or equal to the minimum hysteresis.
Due to the requirements listed above, it may be
necessary to vary the order of the setpoints for a
successful teach-in.
An active teach process in indicated by illumination of the
red LED. If the red LED flashes, the currently pending
measurement value is outside of the validity range (IO-Link
process) or a manual teach was not possible.
Hyst.
High
SP1
Measurement
value
english
27