Overview of IO-Link Data and Functions (continued)
3.6

Events

Event Code
Event Type
0x1850
Notification
(6224)
0x1851
Notification
(6225)
0x1852
Warning
(6226)
0x4000
Error
(16384)
0x4210
Warning
(16912)
0x4220
Warning
(16928)
0x5110
Warning
(20752)
0x5111
Warning
(20753)
0x8CD0
Warning
(36048)
0x8CD1
Warning
(36049)
0x8CFF
Warning
(36095)
0x8D07
Warning
(36103)
0x8D08
Warning
(36104)
0x8D09
Warning
(36105)
0x8D0B
Warning
(36107)
0x8D0E
Notification
(36110)
0x8D10
Warning
(36112)
0x8D12
Warning
(36114)
0x8D13
Warning
(36115)
22
english
Description
Process data profile selection cannot be used –
default value is used.
Process Data Update Timeout – for information
purposes only
Multiple Process Data Update Timeout – for
information purposes only
Temperature Fault – Overload – The device is
operated outside of the device-specific temperature
limits. Risk of device damage.
Device Temperature Overrun – Clear Heat Of Source
– Risk of device damage. The device is too hot.
► Remove heat source, provide the device with
heat insulation if necessary.
Device Temperature Underrun – Insulate Device –
Risk of device damage. The device is too cold.
► Insulate the device.
Primary supply voltage exceeded
► Check for deviations in the supply.
Primary supply voltage below minimum value
► Check for deviations in the supply.
Inclination alarm
► Check installation.
Vibration alarm
► Check machine.
Low signal quality level
The calculation of the basic statistics was stopped
automatically to avoid a buffer overflow.
Speed value is below the limit.
Speed value is above the limit.
Overload or short circuit at pin 2
► Check wiring.
The time has elapsed. This event reports the timeout
of the minimum value/maximum value/average
calculation.
It does not report a timeout for the calculation of the
moving average because the timer repeats and it
does not indicate the end of the calculation.
Device Temperature Upper Warning – The set upper
temperature warning threshold has been exceeded.
The defined threshold of the device-internal humidity
was exceeded.
► Check installation and ambient conditions.
One or more extreme conditions present.
Device Status
0 – Device is operating properly.
0 – Device is operating properly.
0 – Device is operating properly.
4 – Failure
2 – Out-of-Specification
2 – Out-of-Specification
2 – Out-of-Specification
2 – Out-of-Specification
1 – Maintenance-Required
0 – Device is operating properly.
0 – Device is operating properly.
0 – Device is operating properly.
0 – Device is operating properly.
0 – Device is operating properly.
2 – Out-of-Specification
0 – Device is operating properly.
0 – Device is operating properly.
1 – Maintenance-Required
0 – Device is operating properly.