Operating instructions

S 3004 / S 3004 P heating system

d
c
i
f
a = Control knob (thermostat)
b = Piezo push ignitor (S 3004 P)
c = Blind cover
d = Integrated control panel for a Truma fan TEB-3
e = Sensor button to switch on the lighting (optional)
f = Automatic ignition device with battery compartment
(S 3004)
g = Mica window to observe the flame
h = Thermostat sensor
i = Type plate (remove cover!)
The illustration shows installation on the right. For instal-
lation on the left, the parts are arranged on the other side
(mirror-image).

S 5004 heating system

d
c
i
f
a = Control knob (thermostat)
b = Integrated control panel for a Truma fan TEB-3
c = Integrated control panel for second Truma fan TEB-3
d = Blind cover
e = Sensor button to switch on the lighting (optional)
f = Automatic ignition device with battery compartment
g = Mica window to observe the flame
h = Thermostat sensor
i = Type plate (remove cover!)
The illustration shows installation on the right. For instal-
lation on the left, the parts are arranged on the other side
(mirror-image). One or two fans can be mounted. A special in-
stallation box can be supplied for the installation of two fans.
10
b
a
e
h
g
b
a
e
h
g

Taking into operation

S 3004 P with Piezo push ignitor

1. Open gas cylinder and quick-acting valve in the gas supply
line.
2. Turn the control knob (a) into thermostat position 1 – 5 and
push down far as possible. Press the ignitors in quick succes-
sion at the same time until the flame burns.
0
1
5
4
2
3
3. Hold down the control knob (a) for up to 10 seconds so that
the safety pilot responds.
4. Watch another 10 seconds through the mica window
whether the flame is extinguished by the air in the line
(caused by gas cylinder change).
Never re-ignite before waiting another 3 minutes
otherwise there is the danger of deflagration! This
also applies if a heating system already in operation goes out
and needs to be re-ignited.
If the gas supply line is filled with air, it can take up to two
minutes until the gas is ready to burn. Keep the control knob
pressed down and keep pressing the ignitor until the flame
burns.
5. In order to achieve even and quick distribution of warm air
and reduction of the surface temperature at the outlet grill for
warm air, we recommend that the heating system is operated
with the Truma warmer running.
The S 3004 P heating system (with Piezo push ignitor) is
constructed so that subsequent installation of an auto ig-
nitor is possible part no. 30580-01).

S 3004 / S 5004 with auto ignitor

Make sure that a battery is inserted before commissioning for
the first time (see „Battery change on auto ignitor")!
1. Open gas cylinder and quick-acting valve in the gas supply
line.
2. Turn the control knob (a) into thermostat position 1 – 5 and
push down far as possible. Ignition takes place automatically
(audible ignition) until the flame burns.
0
1
5
4
2
3
Hold down the control knob for up to 10 seconds so that the
safety pilot responds.
Wait min. 3 minutes before re-igniting after a fault,
otherwise there is the risk of deflagration!
O
5
a
1
4
2
3
b
O
5
a
1
4
2
3