Cables longer then 6 m are not recommended.
Cable eyes with M6/8 holes should be used.
For supply connection use wires suitable for at least 75°C (167°F).
CAUTION: Replace defective cords or wires immediately.
Connection sequence
• Disconnect mains.
• Disconnect battery cables from the battery.
• Open front cover.
• Connect battery cables to the charger. Note that there's only one
"minus"- Use a fuse according the size of the battery charger.
• Connect battery cables to the battery.
• Connect the AC-in by means of a 3-core cable of 2.5 – 4 mm²
flexible core to the AC-in terminal block. Note that a real PE-
connection is strictly necessary.
• Close the front panel.
Charge voltage at appr. 10% of the nominal current
Absorption
12V
GEL
14.2
AGM
14.35
LA
14.5
Other
14.85
Important note regarding charge voltage settings
The charge voltages as mentioned above for the different types of
battery are indicative only. Please contact your battery supplier for
advice.
Especially flooded lead acid batteries ("LA" in the table) may
require a different charge voltage, depending on
chemical/mechanical construction.
8
Float
24V
12V
28.4
13.5
28.7
13.3
29.0
13.5
29.7
13.7
24V
27.0
26.6
27.0
27.4