Herunterladen Inhalt Inhalt Diese Seite drucken

Connection For Outlet Of Air In Adjacent Rooms; Maintenance; Cleaning The Air Filter Fpan Grille - Daikin FWH-AT Installations-, Bedienungs- Und Wartungsanleitung

Inhaltsverzeichnis

Werbung

8.5
CONNECTION FOR OUTLET OF AIR IN
ADJACENT ROOMS
The units are equipped with 2 rectangular air outlets for connec-
tion to separate distribution ducts.
Ū These outlets are located on the sides not occupied by the
electrical box and water connections.
Ū The PPAI02A/6A accessory is available: a plenum to connect
the rectangular outlets located on the unit to the round dis-
tribution ducts with diameter D:
Model
FWH-A 02-03-04
FWH-A 06-07-08
B
WARNING: The air ducts from the fan coil unit must be ther-
mally insulated to prevent the formation of surface conden-
sation.
9

MAINTENANCE

For safety reasons, before carrying out any maintenance or
cleaning jobs, turn off the unit by moving the fan speed se-
lector to "OFF" and putting off the main switch 0 (OFF).
Any work must be carried out by personnel qualifi ed and au-
thorised to work on this type of unit.
A
DANGER!
Due caution must be taken while carrying out
maintenance: some metal parts may cause injuries; wear
protective gloves.
The material must undergo maintenance in order to retain its
characteristics over time. Lack of maintenance may have the ef-
fect of voiding the product warranty. The operations consist of
cleaning the air fi lter, the internal and external exchangers, the
cabinet, and cleaning and protecting the condensate drip trays.
Odour treatment and disinfection of the surfaces and spaces al-
so contribute to the healthiness of the air breathed by users.
Whenever starting up the unit after it has not been used for a
long time, check that there is no air in the heat exchanger.
Before the period of operation in the cooling mode, check that
condensate is properly drained.
Adequate periodic maintenance will ensure save both ener-
gy and cost savings.
9.1

CLEANING THE AIR FILTER FPAN GRILLE

Clean the air fi lter at least once a month and in any case at the
start of the period of use (before the heating and the air condi-
tioning season).
For fi lter cleaning, proceed as follows (Fig.21 ):
1. Before performing any work on the unit, disconnect it from
the power supply.
2. Remove the screws (1) securing the retainers (2) on each
side.
3. To open the grille (3), push on the two retainers (2) in the
direction of the arrow.
36
FWH-AT/AF
D
150
180
» PPAI02A/6A
4. Open the grille (3) downwards.
5. Remove the fi lter (4) from the grille.
6. Use a vacuum cleaner to remove dust. If dust is glued to the
fi lter, remove it with clean or soapy water, rinse the fi lter with
clean water and dry it.
7. Put the fi lter back into its place in the grille, close the grille,
moving the two retainers outwards, then put the screws se-
curing the retainers back in place.
It is recommended to replace the air fi lter once a year, using an
original replacement fi lter; the indoor unit model can be found
on the identifi cation plate located on the tank inside the unit,
behind the air fi lter.
» Fig�21

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Fwh-af

Inhaltsverzeichnis