Instance Attributes (Instances 1-32)
Instance value 1-32 is equal to Pluto station address 0-31.
Attribute ID Name
1
Input Bits
2
Output Bits
3
Global Bits
4
Combined 32 Bits
10
Additional Data 32 Bits
Common Services
Service
Code
Class Level
0E

HEX

10
HEX
32
HEX
33
HEX
34
HEX
C.8.1 Service Code 0x32
This service code will read local data from the selected Pluto unit.
Instance value 1-32 is equal to Pluto station address 0-31.
Request Service Code Data
Bytes
Description
0 – 1
UINT16, Address value
For more information regarding Pluto address range see chapter 5.4.3.4. Local data from Pluto can
be of 3 different types. The local address data shall be coded with type information in bits 14 and
15 of the address value according to table below.
Bit 15
Bit 14
0
0
0
1
1
0
1
1
Response Service Code Data
The respond value is always a UINT32 value even if the requested data is retrieving Boolean or
UINT16 value. These values are converted into UINT32 value.
Bytes
Description
0 – 3
UINT32, Response value
Implemented for
Instance Level
Yes
Yes
Yes
No
No
Yes
No
Yes
No
Yes
Data Type
Global memory (0/1)
Local memory (0/1)
Local Register (uint16)
Local Parameter (uint32)
108
Data Type
Default
Data Value
WORD
0
BYTE
0
WORD
0
DWORD
0
DWORD
0
Service Name
Get Attribute Single
Set Attribute Single
Read Local Pluto Data
Read Local Gateway Data
Serial Pass Through
Address (range)/value
(0 – 31)
(0 – 1024) | 0x4000
(0 – 300) | 0x8000
(0 – 999) | 0xC000
Access
Rule
Get
Get
Get
Get
Get