C.8 Application Object (64
Class Attributes (Instance 0)
For more information about "Data to Pluto" structure see chapter 4.4.
Attribute ID Name
1
Revision
10
Expected Nodes Bitmap
Not used!
11
Node Status Bitmap
12
Data to Pluto 1
13
Data to Pluto 2
14
Data to Pluto 3
15
Data to Pluto 4
16
Enable Data to Pluto
(0 = Disabled; 1 = Enabled)
Bit 0 – Data To Pluto 1
Bit 1 – Data To Pluto 2
Bit 2 – Data To Pluto 3
Bit 3 – Data To Pluto 4
17
Data to Pluto Timeout (ms)
0 = timeout disabled
Valid value ≥ 1000 ms.
18
Data to Pluto Update Time
(ms). Value modulus of 4 e.g.
0, 4, 8, 16... 252.
19
Gateway node address (0-16)
0 = DIP-switch setting
1 = Node address 0
2 = Node address 1
...
16 = Node address 15
Additional data configuration see chapter 4.3.
Attribute ID Name
32
Additional Data 00, Node (0-31)
33
Additional Data 00, IO-type
34
Additional Data 01, Node (0-31)
35
Additional Data 01, IO-type
36
Additional Data 02, Node (0-31)
37
Additional Data 02, IO-type
38
Additional Data 03, Node (0-31)
39
Additional Data 03, IO-type
40
Additional Data 04, Node (0-31)
41
Additional Data 04, IO-type
42
Additional Data 05, Node (0-31)
43
Additional Data 05, IO-type
44
Additional Data 06, Node (0-31)
45
Additional Data 06, IO-type
46
Additional Data 07, Node (0-31)
47
Additional Data 07, IO-type
32 Instances)
HEX -
Data Type
UINT
DWORD
DWORD
UINT[3]
UINT[3]
UINT[3]
UINT[3]
BYTE
UINT16
UINT8
UINT8
Data Type
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
106
Default
Access
Data Value
Rule
1
Get
0
Get/Set
0
Get
0,0,0
Get/Set
0,0,0
Get/Set
0,0,0
Get/Set
0,0,0
Get/Set
0
Get/Set
0
Get/Set
100
Get/Set
0
Get/Set
Default
Access
Data Value
Rule
0
Get/Set
0
Get/Set
0
Get/Set
0
Get/Set
0
Get/Set
0
Get/Set
0
Get/Set
0
Get/Set
0
Get/Set
0
Get/Set
0
Get/Set
0
Get/Set
0
Get/Set
0
Get/Set
0
Get/Set
0
Get/Set
2TLC172009M0110_D