10.12.2.1. Antibacterial / thermal disinfection cycle
"ANTI BACT."
"ANTI BACT." cycle factory setting: "NO"
Water temperature "TEMP. SETT." factory setting:
"60 °C"
anti bact.
no
Select temperature
temp. sett.
6 0 °
C
Confirm
Example setting:
"ANTI BACT.": 8
"TEMP. SETT.": 60 °C
This means that thermal disinfection is performed
every 8 days at a water temperature of 60 °C.
NOTE
The thermal disinfection is always performed at
22:00.
Press the
button to return to the home screen.
NOTE
If the setpoint for the domestic hot water is already
set to 60 °C (see "Setting the water temperature"
chapter), no antibacterial cycle is initiated as it is car-
ried out continuously.
If the thermal disinfection cycle using the additional
heating element is blocked by a utility company block-
ing signal, it is started again in the next release period.
NOTE
For energy use reasons, thermal disinfection should
only be switched on for a longer period of absence of
3 days or more (e.g. holiday).
EN-22
Select number of days
anti bact.
8 D
Confirm
10.12.2.2. Fan mode "FAN MODE"
"FAN MODE" factory setting: "1"
fa n m o de
Normal operation, automatic fan speed
Mode 1:
Forced ventilation, maximum fan level
Mode 2:
Fan speed during heating-up phase and
Mode 3:
simultaneous external control. e.g. by room
or humidity sensor (e.g. Stego EFR 012)
Press the
button to return to the home screen.
10.12.2.3. Minimum domestic hot water
temperature "T°C MINI"
It is possible to enable the supplementary electric
heating at the same time as the heat pump to prevent
the water temperature falling below the felt comfort
temperature of 38 °C. The supplementary electric
heating is enabled until the water in the cylinder has
reached a temperature of 43 °C.
T °C MINi
no
The function is disabled by default.
With load shedding, this function is not enabled or has
no effect.
Press the
button to return to the home screen.
NOTE
The hysteresis of the domestic hot water heat pump is
5 Kelvin. As soon as the value is below this, the heat
pump goes into reheating mode.