Herunterladen Inhalt Inhalt Diese Seite drucken

Ul-Gerechte Installation; Short Circuit Current Rating - SEW-Eurodrive MOVIMOT advanced DRN DBC-Serie Produkthandbuch

Mechatronische antriebseinheit
Vorschau ausblenden Andere Handbücher für MOVIMOT advanced DRN DBC-Serie:
Inhaltsverzeichnis

Werbung

Projektierung Antriebseinheit
5

UL-gerechte Installation

5.6
UL-gerechte Installation
5.6.1
Field Wiring Power Terminals
5.6.2

Short Circuit Current Rating

148
Produkthandbuch – MOVIMOT
HINWEIS
Folgendes Kapitel wird unabhängig von der Sprache dieser Dokumentation aufgrund
von UL-Anforderungen immer in englischer Sprache abgedruckt.
Observe the following notes for UL-compliant installation:
The devices are for use only in industrial machinery NFPA 79 applications.
For use in a Pollution Degree 1 or Pollution Degree 2 environmental only.
Use 75 °C copper wire only.
Tighten terminals to 17.7 – 21.24 in-lbs (screw connect terminals only).
Suitable for use on a circuit capable of delivering not more than 65,000 rms symmetri-
cal amperes when protected by 600  V nonsemiconductor fuses (Class CA, CB, CD,
CF, G, J, K-1, K-5, RK1, RK5, T) or when protected by 500 V minimum inverse time
circuit breakers having an interrupting rating not less than 65 kA rms symmetrical am-
peres.
®
For MOVIMOT
advanced, when used with optional Load Disconnect Switch:
Suitable for use on a circuit capable of delivering not more than 5,000 rms symmetri-
cal amperes when protected by 600  V nonsemiconductor fuses (Class CA, CB, CD,
CF, G, J, K-1, K-5, RK1,RK5, T) or when protected by 500  V minimum inverse time
circuit breakers having an interrupting rating not less than 5 kA rms symmetrical am-
peres.
The max. voltage is limited to 500 V.
Suitable for motor group installation on a circuit capable of delivering not more than
65,000  rms symmetrical amperes when protected by, 600  V maximum nonsemicon-
ductor fuses (Class CA, CB, CD, CF, G, J, K-1, K-5, RK1, RK5, T) or when protected
by 500 V maximum inverse time circuit breakers having an interrupting rating not less
than 65 kA rms symmetrical amperes.
®
For MOVIMOT
advanced, when used with optional Load Disconnect Switch:
Suitable for motor group installation on a circuit capable of delivering not more than
5,000 rms symmetrical amperes when protected by, 600 V maximum nonsemiconduc-
tor fuses (Class CA, CB, CD, CF, G, J, K-1, K-5, RK1, RK5, T) or when protected by
500  V maximum inverse time circuit breakers having an interrupting rating not less
than 5 kA rms symmetrical amperes.
The max. voltage is limited to 500 V.
®
advanced

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Movimot advanced dr2c dbc-serie

Inhaltsverzeichnis