8
Performance/coefficient of performance (COP)
8.1
SCOP (seasonal coefficient of performance (COP)) average climate 35°C/55°C
8.2
ŋ
average climate 35°C/55°C
s
8.3
Heat output/coefficient of performance (COP)
8.4
Cooling capacity/coefficient of performance (COP)
1. For air temperatures between -22°C and -1°C, flow temperature increasing from 45°C to 64°C.
2. The minimum achievable flow temperature depends on the current volume flow, the set return set temperature and the current performance level.
3. In 2-compressor operation with A35/W12 and A35/W8, this results in a cooling water temperature difference of 5K ±1K.
4. The heat output and COP is reduced by approx. 5% in lower operation
5. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 55°C.
The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A) depending on the installation location.
6. Note that additional space is required for pipe connections, operation and maintenance
7. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, the bivalence point and the regulation should be
taken into consideration. These figures are only achieved with clean heat exchangers. Instructions for care, commissioning and operation can be found in the relevant sections
of the installation and operation instructions. The specified values have the following meaning, e.g. A7/W35: Heat source temperature 7°C and heating water flow temperature
35°C.
8. See CE declaration of conformity
9. The heat circulating pump and the heat pump manager must always be ready for operation.
www.glendimplex.de
Type and order code
7
heat source/heat sink
Air/water
performance level
with A-7/W35
with A2/W35
with A7/W35-30
with A10/W35
with A7/W45-40
with A7/W55-47
7
heat sink/heat source
Air/water
performance level
with A35/W23-18
with A27/W18
with A35/W17-12
with A35/W10
with A27/W12
with A27/W10
452166.66.14 · FD 0008
kW/--
kW/---
kW/--
kW/--
kW/--
kW/--
kW/--
kW/--
kW/--
kW/--
kW/--
kW/--
English
LA 33TPR
4.32/3.54
170/139
EN 14511
1
2
11.0/3.4
19.9/3.1
13.3/4.0
22.2/3.7
16.2/4.9
17.3/5.2
15.8/4.0
15.4/3.4
Direct current
1
2
12.1/2.6
25.3/2.4
12.7/3.0
27.1/2.9
21.5/2.2
10.2/2.3
23.1/2.6
10.8/2.7
EN-19