Use

LL: it is possible to select two operating speeds, V1 and V2, via 2 external switches. The values of V1 and V2
are set in the factory.
LL TP: the appliance provides two operating modes that can be activated manually via external switches
(hereinafter "mode 1" and "mode 2"), plus a fully automatic mode (hereinafter mode 3).
Mode 1: the motor starts up at speed V1 (minimum or maximum, as set during configuration), after a delay,
from the moment of turning on switch 1, of 0, 45, 90, or 120 seconds. The motor will switch off after a run time
of 6, 10, 15, or 21 minutes from the moment of turning off switch 1.
Instead of the switch it is possible to use a button, which must be pressed for at least 0.5 sec.
Note for the installer: if using the button you need to set the appliance switch-on delay to 0.
Mode 2: the motor starts up immediately, via the action of switch 2:
the operating speed is V2 (minimum or maximum, as set during configuration). Again using switch 2, the motor
will stop immediately. This mode is disabled when modes 1 and 3 are active.
Mode 3: fully automatic operation: the motor starts automatically, on V1 (minimum or maximum, as set during
configuration), after a period of non-operation at the same speed, of 0, 8, 12, 24 hours. The motor will stay on
for a period of 6, 10, 15 or 21 minutes. All the variable parameters, whose possible values are listed above,
take on a fixed value set at the time of installation, based on the user's needs and the type of installation.
LL TP HCS: on this model the PCB is connected to a humidity sensor. The appliance provides two operating
modes: "Timer" operation and "HCS Off" operation. One of these two types of operation must be chosen
during configuration.
TIMER operation
The appliance provides two operating modes that can be activated manually via external switches (hereinafter
"mode 1" and "mode 2"), plus two fully automatic modes (hereinafter "mode 3" and "mode 4")
Mode 1: similarly to model LL TP, the motor is started on speed V1 (minimum or maximum, as set during
configuration) by pressing switch 1, after a delay of 0 or 45 seconds. The motor will switch off after a run time
of 6, 12, 18, or 24 minutes. Instead of the switch it is possible to use a button, which must be pressed for at
least 0.5 sec.
Note for the installer: if using the button you need to set the appliance switch-on delay to 0.
Mode 2: as for model LL TP, pressing switch 2 starts the motor immediately: the operating speed is V2
(minimum or maximum, as set during configuration). With switch 2, you can also stop the motor immediately.
Mode 3: the motor will start automatically when the humidity sensor detects relative humidity greater than or
equal to a threshold level of 60%RH, 70%RH, 80%RH, 90%RH. The operating speed is V1 (minimum or
maximum, as set during configuration). The motor will stop when the humidity drops by a value of 15 compared
to the threshold value (e.g. from 60%RH to 45%RH)
In order to avoid continuous day and night operation of the extractor fan, in the event of bad weather, when
the system would not be able to reduce the humidity with ventilation, the appliance behaves as follows:
if the humidity does not drop by 15% RH under the set threshold within 2 hours of operation, the appliance will
switch off for a time of 8 hours. From this moment onwards, in order to ensure a minimum flow of air, the
appliance will run on/off cycles (2 hours on, 8 hours off). When the relative humidity drops by 15% RH under