Dependencies of F-AI 4xI 0(4)..20mA 2-/4-wire HF
(6ES7136-6AA00-0CA1) as of firmware version V1.0.2
Note
If the F-module is not visible in the module selection after the installation of the GSDML, check whether your configuration
software supports the GSDML specification V2.35 or higher.
Reintegration after a channel fault depends on the F-host used. You can find information on this in the documentation of the
F-host.
In the module parameters, you can set the reintegration method a channel at a time. Manual or automatic reintegration is
possible. When configuring with GSD file, only module-wide passivation is possible.
With configuration by GSD file, the F-module supports PROFIsafe V2.6MU1. An F-host is required which also supports a
PROFIsafe V2.6MU1 or higher.
With "Evaluation of the sensors" with the setting "1oo1 evaluation (max. SIL3/Cat.3/PLd)"
The following parameters do not have any influence on the measured values and can be ignored.
Standard value
Discrepancy time
Tolerance window % absolute
Tolerance window % relative
With "Evaluation of the sensors" with the setting "1oo2 evaluation (max. SIL3/Cat.4/PLe)"
When switching from 1oo1 evaluation to 1oo2 evaluation, you have to activate the two corresponding channels.
The following parameters must have the same settings for the primary and secondary channel:
Channel failure acknowledge
Measuring range
Diagnostics: Wire break
Smoothing
Note
For the measuring range 0...20 mA, you have to activate the parameter "Diagnostics: Wire break".
Dependencies of F-AI 4xU 0..10V HF (6ES7136-6AB00-0CA1)
Note
If the F-module is not visible in the module selection after the installation of the GSDML, check whether your configuration
software supports the GSDML specification V2.35 or higher.
Reintegration after a channel fault depends on the F-host used. You can find information on this in the documentation of the
F-host.
In the module parameters, you can set the reintegration method a channel at a time. Manual or automatic reintegration is
possible. When configuring with GSD file, only module-wide passivation is possible.
With configuration by GSD file, the F-module supports PROFIsafe V2.6MU1. An F-host is required which also supports a
PROFIsafe V2.6MU1 or higher.
Dependencies during configuration with GSD files for ET 200SP fail-safe modules
A5E32311847-AD, 04/2022