Dependencies for 1oo2 evaluation
Both channels must be activated.
The "Input delay" parameter must be identical for each pair. The "Input delay" parameter for the channel pair is determined as
follows:
"Input delay" < MIN("Input delay" for channel n, "Input delay" for channel n+4).
The configured discrepancy time must be greater than the configured input delay.
Disable chatter monitoring for both channels.
Dependencies F-DI 8x24VDC HF (6ES7136-6BA01-0CA0)
The same dependencies apply to this F-module as for F-DI 8x24VDC HF (6ES7136-6BA00-0CA0).
In addition, channel-by-channel passivation is also possible due to the support of PROFIsafe V2.6MU1.
Dependencies for safety mat evaluation (from firmware version V2.0.0)
If you have configured a channel group as a safety mat evaluation, you must assign the sensor supplies to the digital inputs
as follows:
VS
to DI
and VS
to DI
0
0
4
VS
to DI
and VS
to DI
1
1
5
VS
to DI
and VS
to DI
2
2
6
VS
to DI
and VS
to DI
3
3
7
The short-circuit test must be activated on both sensor supplies.
You must set the parameters "Time for short-circuit test" and "Startup time of sensor after short-circuit test" to 4.2 ms.
Both channels must be activated.
You must set the parameter "Input delay" to the fixed value 1.6 ms for each channel of the channel pair.
Disable chatter monitoring for both channels.
The parameter "Channel failure acknowledge" must have the same value for both channels of the channel pair.
Dependencies F-PM-E 24VDC/8A PPM ST (6ES7136-6PA00-0BC0) as
of firmware version V2.0.0
The same dependencies apply to this F-module as for the two F-modules with article numbers 6ES7136-6DB00-0CA0 and
6ES7136-6BA00-0CA0 described above.
In TIA Portal, the "IO Tags" tab displays more tags than supported by the F module.
Dependencies F-DQ 8x24VDC/0.5A PP HF (6ES7136-6DC00-0CA0)
If you have enabled "Disable dark test for 48 hours", you must configure the "Max. readback time light test / dark test"
parameter the same for all channels.
Reintegration after a channel fault depends on the F-host used. You can find information on this in the documentation of the
F-host. The F module supports configuration per GSD file PROFIsafe V2.4.
When configuring with GSD file, only module-wide passivation is possible.
Dependencies F-RQ 1x24VDC/24..230VAC/5A (6ES7136-6RA00-
0BF0)
The F module has no F_iPar_CRC and no PROFIsafe address. You do not need to assign a PROFIsafe address to the F module.
If you nevertheless assign a PROFIsafe address to the F module with S7-FCT, an error message is displayed.
8
4
5
6
7
Dependencies during configuration with GSD files for ET 200SP fail-safe modules
A5E32311847-AD, 04/2022