Siemens SIMATIC ET 200SP Produktinformation Seite 10

Vorschau ausblenden Andere Handbücher für SIMATIC ET 200SP:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
With "Evaluation of the sensors" with the setting "1oo1 evaluation (max. SIL2/Cat.3/PLd)"
The following parameters do not have any influence on the measured values and can be ignored:
Standard value
Discrepancy time
Tolerance window % absolute
Tolerance window % relative
With "Evaluation of the sensors" with the setting "1oo2 evaluation (max. SIL3/Cat.4/PLe)"
When switching from 1oo1 evaluation to 1oo2 evaluation, you have to activate the two corresponding channels.
The following parameters must have the same settings for the primary and secondary channel:
Channel failure acknowledge
Diagnostics: Wire break
Smoothing
Note
If the above-mentioned condition is not met, a parameter assignment error occurs or the parameter assignment is refused.
Siemens AG
Digital Industries
Postfach 48 48
90026 NÜRNBERG
GERMANY
Dependencies during configuration with GSD files for ET 200SP fail-safe modules
A5E32311847-AD, 04/2022
10
Dependencies during configuration with GSD files for ET 200SP fail-safe modules
A5E32311847-AD, 04/2022