Herunterladen Inhalt Inhalt Diese Seite drucken

GEA Grasso V Serie Installations- Und Wartungsanleitung Seite 47

Hubkolbenverdichter für die industrielle kühlung
Inhaltsverzeichnis

Werbung

4.
5.
6.
Oil and oil return systems:
The quality of the oil effects the oil consumption and the life time of the moving
parts. For oil return systems or systems in which soluble oil is being used, check
(or have checked) the quality of the oil every 5000 hours is strongly advised and -
if necessary - to renew the oil and/or filters. If there is no oil analysis available,
renewal of the oil is advised. By regularly carrying out oil analyses and registering
them in a log, aberrations will be noticed in an early stage, which may prevent or
reduce resultant damage(s).
Notes;
1.
2.
0089388_imm_v_german_~_20
26.07.2021
Measuring means also that visual inspection is required.
Visual inspections:
The visual inspections during maintenance are of importance; measurements
should be carried out at the moment that visually abnormalities are detected.
The result of the inspection determines whether one or more parts have to be
replaced. For more detailed information refer (SIM) and Installation and Main-
tenance Manual (IMM).
Oil and oil return systems:
The quality of the oil effects the oil consumption and the life time of the
moving parts. For oil return systems or systems in which soluble oil is being
used, we advise to check (or have checked) the quality of the oil every 5000
hours and - if necessary - to renew the oil and/or filters. If there is no oil analy-
sis available, we advise to renew the oil. By regularly carrying out oil analyses
and registering them in a log, aberrations will be noticed in an early stage,
which may prevent or reduce resultant damage(s).
Note 1:
When renewing the oil, in the crankcase the oil in the oil separator and the oil
return or oil rectifier system (if fitted) has to be renewed.
Note 2:
Pre-lubricate the compressor before re-starting. Used or filtered oil should
NEVER be added to a compressor under any circumstance. Use only new oil
as selected from the Grasso oil table. Oil charging via the suction line of the
compressor is not allowed.
When renewing the oil, in the crankcase the oil in the oil separator and the oil
return or oil rectifier system (if fitted) has to be renewed as well.
Pre-lubricate the compressor before re-starting. Used or filtered oil should
never be added to a compressor under any circumstance. Use only new oil as
selected from the Grasso oil table. Oil charging via the suction line of the
compressor is not allowed.
SERVICEWARTUNGSÜBERSICHTEN
WARTUNG
47

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis