Fireplace flue gas
Avoid
contact
with
(example: wooden beams) and in any case provide
for their insulation with flame retardant material.
In case of pipe penetrations through roofs or
walls is recommended to use special kits crossing,
certificates, are available commercially. In the event
of a chimney fire, turn off the stove, disconnect
from the network and never open the door. Then
call the authorities.
The chimney cap
The chimney cap must respect the following re-
quirements:
• It must have the equivalent diameter and inter-
nal form
of the flue.
• It must have a useful outlet diameter of not less
than double that of the flue.
• The chimney cap on the roof or that remains in
contact with the outside (for example, in case of
open lofts or attics), must be covered with ele-
ments in brick or tile and must, in any case, be
well insulated.
• It must be constructed to prevent rain, snow, and
extraneous bodies from entering the flue and so
that the discharge of the products of combus-
tion is not inhibited by wind from any quarter or
strength (wind-proof chimney cap).
• The chimney cap must be positioned in such a
way as to guarantee the adequate dispersion
and dilution of the products of combustion and
in any case, must be out of the reflux zone. This
zone has different dimensions and forms accord-
ing to the angle of inclination of the roof so it is
necessary to adopt minimum heights (Fig. 2).
• The chimney cap must be a wind-proof type and
must be above the ridge.
• Eventual structures or other obstacles that are
higher than the chimney cap must not be too
close to the chimney cap itself.
• The device should not be installed in the flue
shared.
combustible
materials
YES
Connection of the canalization pipe
You will be able to connect to the air exit on the
back of the stove only one tube of 80mm diameter
and 8 linear meters of maximum length.
You have to consider a loss around 1 meter of the
linear tract for each bend of 45° (ex.: maximal
distance without bends: 8 meters; maximal
distance with one bend 8-1=7 meters).
Distance to objects
It is also recommended to keep the pellets and all
flammable materials at a suitable distance from
the stove.
20 cm
40 cm
NO
100 cm
7