Fig. 2.1 Replacing the venturi and mass fl ow sensor
► Disconnect the air intake pipe.
► Remove the connectors from the sensor of the venturi (1,
fi g. 2.1) by depressing the detent.
► Unscrew the union nut (3) of the gas connection pipe (2)
on the gas fi tting.
► Take the venturi with the gas connection pipe from the
fan by turning the venturi bayonet lock anti-clockwise to
its fullest extent and removing it from the ventilator.
7
6
5
4
Fig. 2.2 Dismantling the gas connection pipe
0020161081_05
► Dismantle the gas connection pipe (1, fi g. 2.2) from the
1
2
► Remove the gas nozzle (6) straight ahead and dispose.
► Check whether the venturi is free of residue.
a
3
► Install the gas nozzle in the venturi in accordance with
Tab. 2.1 colour coding of the gas nozzles
b
When installing the gas nozzles, ensure their correct
alignment using the position markers on the upper side
of the venturi and the locating pins (5, fi g. 2.2) on the
underside of the gas nozzle.
If this is a group 2 heating device, (s. table 1.2), the
replacement of the gas fi tting is now performed as described
in the following chapter.
If only the gas nozzle in the venturi needs to be replaced
1
(group 1, see table 1.1 and gas conversion within the same
natural gas family), proceed as follows:
► Reinstall the components in the reverse order. Use the
► Change the coded resistance (see chap. 2.3).
2
3
CONVERTING THE GAS GROUP
venturi (3) by removing the clamp (4) and pulling the gas
connection pipe vertically. Dispose of the seal (7).
Danger
Danger of poisoning from
increased CO values.
An incorrect gas nozzle size can
lead to increased CO values.
When replacing the gas nozzle,
ensure that you use the correct
nozzle (colour marking and
position of the pins on the gas
nozzle underside).
the gas group (see tab. 2.1).
Gas group
Colour of
the gas
nozzle
Natural gas G20
Yellow
Propane G31
Grey
Caution.
Risk of damage to the product.
Lubricants can block the function-
relevant channels in the venturi.
Do not use any lubricants when
fitting the gas nozzles.
new seals in the process.
Colour of the
coded resistance
(art.-no.)
Yellow (0020112215)
Grey (0020112214)
23