6.7 - LOW VOLTAGE LIGHT (24V)

The CITY2+ controller has a 24 V DC output that allows
connections to a load up to 15 W.
This output can be used to connect a signal light that indicates
that status of the gate, or for a low voltage flashing light.
Connect the low voltage signal light or flashing light wires to
terminals Z1 (+) and Z2 (-).
m
CAUTION: Pay attention to the polarity of the
connected device if necessary.
6.8 - 230V COURTESY LIGHT OR
FLASHING LIGHT
Thanks to the output COURTESY LIGHT the control unit allows
the connection of an electric appliance (e.g. courtesy light or
garden lights), controlled automatically or by means of the special
transmitter key.
The courtesy light terminals can be alternatively used for a 230V
flashing light with integrated flasher.
CAUTION: When the controller is operating on battery
power, the 230 V flashing light will not work.
The output COURTESY LIGHT is a simple N.O. contact with no
power supply (the maximum rating of the relay is 5A - 230V).
Connect the cables to terminals B1 and B2.

6.9 - LOCK

An electric lock can be assembled on the gate, to ensure a good
closing of doors. Make use of a 12V lock.
Connect lock cables to terminals K9 and K10 of the control unit.

6.10 - LIMIT SWITCH AND ENCODER

The CITY2+ controller can control the gate's travel using a limit
switch and/or an encoder.
m
CAUTION: The use of these devices is strongly
recommended to ensure that the gate opens and closes
correctly.
The speed of operation of the DC motors can be conditioned by
variations in mains power, atmospheric conditions, and friction of
the gate.
Furthermore, encoders also allow the controller to determine if
the gate stops in an irregular position due to an obstacle.
For encoder operation, it is required that the closure position for
each section of the gate be detectable using a limit switch sensor
or a mechanical stop.
Each time the controller is turned on, to realign the encoders, the
gate is closed until it reaches the limit switch or the mechanical
stop.
The control unit supports two kinds of end of stroke:
• end of stroke equipped with a normally close switch that will
be opened as soon as the door reaches its position desired (set
FC.En
the parameter
• end of stroke in series of motor winding (set the parameter
FC.En
Cor.0
=
)
GATES WITH TWO PANELS
For gates with two panels, limit switches and encoders share the
same terminals so it is not possible to install both of these devices
at the same time.
m
PLEASE NOTE: refer to the motor manual
Installation of limit switch
• Connect the open limit switch to motor 1 using terminals
K1 (FCA1) and K5 (COM)
• Connect the close limit switch to motor 1 using terminals
K2 (FCC1) and K5 (COM)
• Connect the open limit switch to motor 2 using terminals
K3 (FCA2) and K5 (COM)
• Connect the close limit switch to motor 2 using terminals
K4 (FCC2) and K5 (COM)
Installation of encoders
• Connect the negative feeds (BLACK cable) for both encoders to
terminal K5 (COM)
• Connect the positive feeds (RED cable) for both encoders to
terminal K6 (+)
• Connect the encoder outputs (BLUE / WHITE) to motor 1 using
terminals K3 (FCA2) and K4 (FCC2)
• Connect the encoder outputs (BLUE / WHITE) to motor 2 using
terminals K1 (FCA1) and K2 (FCC1)