Herunterladen Inhalt Inhalt Diese Seite drucken

CLIVET CEILING & FLOOR 2 IF3-XY 53M Handbuch Für Installation Seite 54

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

2.4.4 Drainage pipe
The drainage pipe is used to drain the water from the
unit. Incorrect installation can cause damage to the unit
and other material damage.
a
CAUTION DANGER
– Insulate all of the pipes to prevent
condensate from forming, which could
cause water damage.
– If the drainage pipe is bent or not installed
properly, the water can escape and cause
the float switch to malfunction.
– In HEAT mode, the outdoor unit discharges
water. Make sure that the drainage pipe is in
a suitable area to avoid water damage and
slipping hazards caused by the discharge
water freezing.
– DO NOT pull the drainage pipe, as this could
detach it.
l
WARNING
A polyethylene pipe (outer diameter =
3.7-3.9cm, inner diameter = 3.2cm) is required
for this installation, which you can find in
hardware shops or from your local dealer.
1 Install the drainage pipe as shown in the figure:
2 Cover the drainage pipe with a heat-insulating material
to prevent condensate and possible water leaks.
16
3 Connect the end of the drainage pipe to the unit's
4 If connecting more than one drainage pipe, follow the
l
1-1.5 m
1/100 slope
Fig. 17
outlet pipe. Wrap the end of the pipe and securely
fasten it with a hose clamp.
Drainage pipe
Metal hose clamp
Drainage pipe
connection hole
installation diagram below:
WARNING
– When using an extension for the drainage
pipe, tighten the connection on the inside
with an additional protection pipe to stop it
from coming loose.
– The drainage pipe must slope by at least
1/100 to prevent the water from flowing back
into the air conditioner.
– To stop the pipe from bending, fix the
suspension elements every 1-1.5 m.
– Incorrect installation can cause the water to
flow back into the unit.
Installation
Insulation
Fig. 18
Fig. 19

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ceiling & floor 2 if3-xy 70mCeiling & floor 2 if3-xy 105mCeiling & floor 2 if3-xy 140mCeiling & floor 2 if3-xy 160m