How to wire
1. Connect the connecting wire to the terminal as
identified with their respective numbers on the
terminal block of indoor and outdoor unit.
H07 RN-F or 60245 IEC 66 (1.5 mm
2. When connecting the connecting wire to the
outdoor unit terminal, prevent water coming in
the outdoor unit.
3. Insulate the unsheathed cords (conductors)
with electrical insulation tape. Process them so
that they do not touch any electrical or metal
parts.
4. For inter connecting wire, do not use a wire
jointed to another on the way.
Use wires long enough to cover the entire
length.
Earth screw
Connecting wire
Stripping length power cord and
connecting wire
10
50
Earth line
17-EN
To Indoor unit
Power supply
terminal block
terminal block
1
2
3
Earth screw
Pipe valve fixing
plate
10
1 2 3
L N
10
50
30
(mm)
Earth line
Connecting wire
• The installation fuse must be used for the power
supply line of this air conditioner.
2
or more)
• Incorrect/incomplete wiring might cause an
electrical fire or smoke.
• Prepare the exclusive power supply for the air
conditioner.
• This product can be connected to the mains.
Connection to the fixed wiring :
A switch which disconnects all poles and has a
contact separation of at least 3 mm must be
incorporated in the fixed wiring.
L
N
Power supply
wire
10
40
Power supply
wire
– 17 –