Herunterladen Inhalt Inhalt Diese Seite drucken

Kampmann KaDeck Montageanleitung Seite 4

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
EN
Assembly instructions
1
Overview
5
7
1
KaDeck at a glance (example shows air discharge on two sides)
2
Safety
This section provides an overview of all important safety aspects for protecting personnel. In ad-
dition to the safety notes in this and the more detailed instruction in accordance with the QR
Code, the occupational health and safety and environmental protection regulations applicable to
the unit's field of application, as well as the notes in accordance with EN60335-1, must be ob-
served.
2.1
Correct use
The units are only intended to be used for heating and cooling air in frost-free and dry rooms.
Within the room, the unit needs to be connected to the building's heating/cooling/ventilation
system and to the building's waste water and power network. The operating limits and limits of
use described in Chapter 2.2 [} 4] must be observed.
IMPORTANT NOTE!
Only use the unique after completion of the complete building and system. Site
heating is not deemed to be correct and proper use.
Intended use of the unit also includes adherence to these instructions.
Any use beyond or other than the stated intended use is considered as misuse.
Any change to the unit or use of non-original spare parts will cause the expiry of the warranty
and the manufacturer's liability.
2.2
Limits of operation and use
Limits of operation
Min./max. water temperature
°C
Min./max. air intake temper-
°C
ature
Min./max. air humidity
%
Min. operating pressure
bar/kPa
Max. operating pressure
bar/kPa
Min./max. glycol percentage
%
SAP 1538177 01/22
6
4
2
3
4-80
6-40
20-60
-
16/1600
0-50
Kampmann GmbH & Co. KG
Friedrich-Ebert-Str. 128-130
E: info@kampmann.de
1
2
3
4
5
6
7
Operating voltage
Power/Current consumption
IMPORTANT NOTE!
Danger of frost in cooling mode!
There is a risk of the heat exchanger freezing when used in unheated rooms.
Protect the unit from frost.
IMPORTANT NOTE!
Warning of misuse!
In the event of misuse, as itemised below, there is a danger of limited or failing
operation of the unit. Ensure that the airflow can circulate freely.
Never operate the unit in humid areas, such as swimming pools, wet areas
etc.
Never operate the unit in rooms with an explosive atmosphere.
Never operate the unit in aggressive or corrosive atmospheres (e.g. sea air).
Never operate the unit above electrical equipment (such as switch cabinets,
computers or other electrical units, or contacts that are not drip-proof).
Never use the unit as a construction site heater.
2.3
Risk from electrocution!
DANGER!
Risk of fatal injury from electrocution!
Contact with live parts will lead to fatal injury from electrocution. Damage to the
insulation or individual components can lead to a fatal injury.
Only permit qualified electricians to work on the electrical system.
Immediately disconnect the system from the power supply and repair it in
the event of damage to the insulation.
Keep live parts away from moisture. This can cause a short circuit.
Properly earth the unit.
Assembly instructions
Assembly, installation and operating
49811 Lingen (Ems)
T: +49591/7108 0
www.kampmann.de
Design panel
Filter
Securing panel
Condensate tray
Suspension bracket
Condensate pump
Electrical junction box
230 V/ 50/60 Hz
On the type plate
KaDeck
instructions:
4

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis