Herunterladen Inhalt Inhalt Diese Seite drucken

Commissioning - Carrier 40VA003D7FAQEE Installations- Und Benutzerhandbuch

Ahu dx kit (ddc-steuerung)
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 105

Commissioning

1. Confirm that the cover of the electrical cabinet of the connection kit is sealed well.
2. Conduct commissioning in accordance with the installation and use specification attached to the outdoor unit.
At the time of energization, because the electronic expansion valve will start initialization (open/ close), there may
be a click lasting for approximately 20 s, which is normal.
Operating Range of AHU Air Return Temperature
Cooling
Max.
DB: 43
Min.
Heating
Max.
Min.
Failure code ---related to AHU DX kit
Failure code at
PCB LED5
wired controller
(connection kit) Fault Descriptions
1
2
3
5
6
7
8
9
20
Connection kit failure code list
Failure code
Fault Descriptions
E1
Indoor ambient temperature Tai sensor
E2
Indoor pipe temperature Tc1 sensor
E3
Indoor pipe temperature Tc2 sensor
E5
EEPROM Error
E6
Communication With Outdoor Unit
E7
Communication With Controller
E9
Repeated address of indoor
o
C WB: 32
o
C
o
WB: 14
C
o
DB: 28
C
o
DB: 5
C
1
Fault of connection kit ambient temp.transducer TA
2
Fault of connection kit pipe temp. transducer TC1
3
Fault of connection kit pipe temp. transducer TC2
5
Fault of connection kit EEPROM
6
Fault of communication between connection kit & outdoor units
7
Fault of communication between connection kit and wired control
8
Fault of connection kit water drainage
9
Fault of duplicate connection kit address
20
Corresponding faults of outdoor units
31

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis