Installation Procedures
Lifting drainpipe
The drainpipe can be lifted 360 mm.
After the drainage pipe has been lifted, it must
be installed with a downward slope.
Confirming drainage
The drainage should be checked during the test run to ensure that there is no
leakage in the connection.
Fill water from the outlet or the specified position and check the drainage.
Fill 600 cc water using a hose from the outlet or the specified location on the
machine. Add the water slowly. Don't add water to the motor of the drainage pump.
• After mounting the electrical system, ensure that cooling occurs adequately and
also introduce water into the system for checking.
• If the electrical installation hasn't been completed, pull out the terminal (2P) of the
floater switch on the electrical cabinet. After confirming the drainage, connect the
terminal of the floater switch, and run the drainage pump for 5 minutes until it
stops automatically.
• Confirm the sound of the motor:
Confirm the sound of the motor of the drainage pump, and meanwhile check the
drainage.