Abschnitt 9
Anhang B | Konfigurationsmodus - Systemkonfiguration
9.16
SLD-CONF – FM auswählen (3)
IEC18000842 V1 EN-US
Siehe
66
Abschnitt
5.5.4.
© 2019 - 2021 Hitachi Power Grids. Alle Rechte vorbehalten
(1) Select BM from table
The 'Bay model import options' menu
appears now, providing the following
selection items:
 BM to be imported with or without
voltage transformer
(If a disturbance recorder with voltage
option, or any voltage function is used,
this item must be selected)
 BM to be imported with or without
PIO's
(6 precision outputs per BU)
 BM to be imported with a set of bay
protection functions (Variant available '
"L-V2")
 BM to be imported with or without
LMI LED configuration
(If the default LED configuration shall be
applied for the local HMI, this item has to
be selected)
(2) Press OK.
1MRK 511 452-UDE Rev. C
GUID-64DD32F2-7DCE-47ED-BFA4-957F86F875D8 v3
Dezentraler Sammelschienenschutz REB500
Engineering-Handbuch