2.7.2 P menus for the user

Menu P1  Status of programmes
Sub-
Description
menu
P11
Is menu 21 currently active?
P12
Is menu 22 currently active?
P13
Is menu 23 currently active?
P14
Is menu 24 currently active?
P15
Is menu 25 currently active?
P16
Is menu 26 currently active?
Menu P2  Setting time delays
Sub-menu
P21
(Optional)
Note:
Only applies to systems
fi tted with a corded switch
and a second switch in the
bathroom.
P22
(Optional)
Note:
Only applies to systems
fi tted with a corded switch
and a second switch in the
bathroom.
P23
(Optional)
Note:
Only applies to systems
fi tted with a hardwired
3-position switch.
P24
P25
Note:
Only applies to systems fi t-
ted with an RF switch.
EN - 10
Description
Delay timer for the bathroom switch (to
switch to high position).
• 'x' minutes after operating the bathroom
switch, the ComfoAir switches to the
.
SETTING
- Low voltage input
Overrun timer for the bathroom switch (to
switch to normal position).
• 'x' minutes after operating the bathroom
switch, the ComfoAir switches back to the
.
NORMAL SETTING
- Low voltage input
Overrun timer for ventilation position 3 (us-
ing an wired 3-position switch).
• If ventilation setting 3 (high) is switched
on briefl y (< 3 sec), the ComfoAir will
switch to the
HIGH SETTING
and then automatically returns to the
.
MAL SETTING
If any 3-position switch is operated during
this lagging time the ComfoAir will instantly
revert to the ventilation position as set at
that time.
Filter warning
• 'x' weeks after cleaning the fi lters the "
" alert will reappear.
TER DIRTY
Overrun timer for ventilation setting 3 (using
"
").
• After pressing "
" briefl y (< 2 sec.), the
ComfoAir will switch to the
'x' minutes and then automatically returns
to the
setting.
NORMAL
If any 3-position switch is operated during
this lagging time the ComfoAir will instantly
revert to the ventilation position as set at
that time.
Yes (1) / No (0)
Yes (1) / No (0)
Yes (1) / No (0)
Yes (1) / No (0)
Yes (1) / No (0)
Yes (1) / No (0)
Minimum
0 Min.
HIGH
0 Min.
0 Min.
for 'x' minutes
-
NOR
10 weeks 26 weeks
-
FIL
1 Min.
setting for
HIGH
Status
Activated
Time delay values
Maxi-
General
mum
Reset
15 Min.
0 Min.
120 Min. 30 Min.
120 Min.
0 Min.
16
weeks
20 Min.
10 Min.