aerospace AC10 series climate control electromechanical filtration fluid & gas handling hydraulics HA502320U001 Issue 3 pneumatics process control Product Manual sealing & shielding ENGINEERING YOUR SUCCESS.
The user must analyze all aspects of the application, follow applicable industry standards, and follow the information concerning the product in the current product catalogue and in any other materials provided from Parker or its subsidiaries or authorized distributors.
English WARNING! - Ignoring the following may result in injury or damage to equipment SAFETY Where there is conflict between EMC and Safety requirements, personnel safety shall always take precedence. Never perform high voltage resistance checks on When replacing a drive in an application and before the wiring without first disconnecting the drive from returning to use, it is essential that all user defined the circuit being tested.
English QUICKSTART BEFORE YOU START This document covers the steps necessary for a basic start up of the AC10 drive. Drive start ups should be performed by competent electrical technicians who are familiar with AC drives and their applications. For detailed installation, safety and applications refer to the Product Manual.
Seite 7
English Product Range Input current (A) Input Output protection Supply Part number Current (A) current 230V 380V/400V 460V/480V 10G-11-0015-XX 10G-11-0025-XX 0.37 10.0 10G-11-0035-XX 0.55 14.0 1Ph 230V 10G-11-0045-XX 0.75 18.1 10G-12-0050-XX 10.8 24.5 10G-12-0070-XX 25.2 10G-12-0100-XX 32.0 10G-31-0015-XX 10G-31-0025-XX 0.37 10G-31-0035-XX 0.55 10.0...
Seite 8
English Drive Start-up Read the Safety section at the front of the QuickStart. Ensure that all local electric codes are met. Check for damage to equipment. Check for loose ends, clippings, filings, drilling swarf etc. lodged in the drive and system. ...
Seite 9
English 30kW – 180kW Basic Wiring Diagram for Three-phase AC drives (NPN type) Keypad LED shows running frequency, flashing target frequency, function code, parameter value or fault code. 4 LEDs indicate working status. RUN while running. FWD running forward and FRQ when the MMI is showing frequency. Press “M”...
Seite 10
English Set-Up Instructions Select the application mode. See Chapter 9 for the application description. Press (M) until F100 is shown on the display Press (O) until only the FWD LED is illuminated (X O X X) Press (UP) to access parameter block F2xx Press (O) until both the FWD and DGT LEDs are illuminated (X O O X) Press (UP) until display shows F228 Press (E) to edit the application number...
English For terminal control please check the selector switiched for the analogue inputs. F203=2, channel AI2 is selected F203=1, channel AI1 is selected SW1 coding switch Coding Coding Mode of Speed 0~10V voltage Switch 1 Switch 2 Control 0~5V voltage 0~10V voltage 0~20mA current Also check the NPN, PNP selector switches for the digital inputs.
Wartungs-, Sicherheits- und Warnanforderungen der Anwendung erfüllt werden. Der Anwender muss alle Aspekte der Anwendung genau untersuchen, geltenden Industrienormen folgen und die Informationen in Bezug auf das Produkt im aktuellen Produktkatalog sowie alle anderen Unterlagen, die von Parker oder seinen Tochtergesellschaften oder Vertragshändlern bereitgestellt werden, zu beachten.
Die Spezifikationen, Beispiele und Schaltungen, wie sie in diesem Handbuch beschrieben sind, dienen nur als Richtlinie und bedürfen gegebenenfalls einer kundenspezifischen Anpassung. Das Anpassen an anwenderspezifische Anlagen oder Systeme liegt außerhalb des Verantwortungsbereichs von Parker Hannifin. RISIKOBEURTEILUNG Bei Störungen, Netzspannungsausfall, Gerätefehlern oder sonstigen unbeabsichtigten Betriebsbedingungen besteht die Möglichkeit, dass das Gerät nicht spezifikationsgemäß...
Deutsch SCHNELLSTARTANLEITUNG ERSTE SCHRITTE In diesem Dokument werden die Schritte beschrieben, die Sie zur Vorbereitung der Inbetriebnahme des AC10-Antriebs durchführen müssen. Die Inbetriebnahme des Antriebs sollte von qualifizierten Elektrotechnikern vorgenommen werden, die mit AC-Antrieben und deren Anwendungen vertraut sind. Ausführliche Informationen zu Aufstellung, Sicherheit und Anwendungen finden Sie im AC10 Produkthandbuch.
Seite 15
Deutsch Produkt-Code - Siehe Seite 1-4 Produktpalette - Siehe Seite 1-5 Inbetriebnahme des Antriebs Lesen Sie die Sicherheitsanweisungen auf der Vorderseite der Schnellstartanleitung. Stellen Sie sicher, dass alle örtlichen elektrischen Vorschriften beachtet werden. Prüfen Sie das Gerät auf Beschädigungen. ...
Seite 16
Deutsch 30kW – 180kW Basic Wiring Diagram for Three-phase AC drives (NPN type) Keypad LED zeigt Lauffrequenz, blinkende Zielfrequenz, Funktionscode, Parameterwert oder Fehlercode. 4 LEDs zeigen Betriebsstatus. RUN beim Laufen. FWD läuft vorwärts und FRQ wenn die MMI zeigt Frequenz. Drücken Sie "M"...
Seite 17
Deutsch 0: Invalid 1: Basic speed control 2: auto/manual control Application selection F228 3: Stage speed control 4: Terminal control; 5: PID control; Anwendung wird als Standard festgelegt, ermöglicht diese den Zugriff auf alle Paramater finden Sie die vollständige Bedienungsanleitung für die Beschreibung aller Operationen. Für Anwendungsverbindung Zeichnungen finden Sie am Ende dieser Kurzanleitung.
Deutsch Testlauf des Umrichters von der Tastatur oder der Terminal-Steuerung, Kontrolle alle Bedingungen sicher sind. Für erweiterte Funktionen finden Sie in der umfassenden Anleitung geliefert. Um alle Paramater Standardwerte zurückzusetzen, um eingestellt F160 = 1 ist. KONFORMITÄT Im vollständigen AC30V Produkthandbuch ist ein umfassender Führer zur Produktkonformität enthalten. Warnung –...
Parker ou ses filiales ou ses distributeurs autorisés. Dans la mesure ou Parker ou ses filiales ou ses distributeurs autorisés fournissent des composants ou des options basées sur des données ou des spécifications fournies par l’utilisateur, l’utilisateur est responsable afin de déterminer que les données et spécifications sont appropriées et suffisantes pour toutes les applications et les utilisations...
Seite 20
Français ATTENTION! - Ne pas prendre en compte ces recommandations peut entraîner blessures ou dommages matériels SECURITE Quand il y a un conflit entre Sécurité et CEM, la sécurité du personnel est toujours prioritaire Les sondes thermiques moteurs doivent être au Ne jamais effectuer de contrôle au mégohmmètre minimum en isolation simple.
Français DÉMARRAGE RAPIDE AVANT DE DÉMARRER Ce document couvre les étapes nécessaires pour un démarrage de base du variateur AC10. Les démarrages du variateur doivent être effectués par des techniciens électriques qualifiés qui connaissent parfaitement les variateurs CA et leurs applications. Pour obtenir plus d'informations sur l'installation, la sécurité...
Seite 22
Français Code de produit – Voir page 1-4 Gamme de produits – Voir page 1-5 Démarrage du variateur Lisez les informations de sécurité au début de ce guide de démarrage rapide. Vérifiez que l'ensemble des normes électriques sont respectées. ...
Seite 23
Français 30kW – 180kW Basic Wiring Diagram for Three-phase AC drives (NPN type) Keypad ED indique fréquence de fonctionnement, fréquence de ignotement de cible, le code de fonction, la valeur de aramètre ou le code d'erreur. 4 LED indiquent l'état de marche. RUN lors de l'exécution. Traction avant la course en avant et FRQ quand l'IHM affiche la fréquence.
Seite 24
Français 0: Invalid 1: Basic speed control 2: Auto/manual control Application selection F228 3: Stage speed control 4: Terminal control; 5: PID control; L'application est définie par défaut, ce qui permet l'accès à tous les paramaters s'il vous plaît voir le manuel complet pour la description de toutes les opérations.
Français Essai de fonctionnement de l'onduleur à partir du clavier ou de la borne de commande, en vérifiant toutes les conditions sont sécuritaires. Pour les fonctions avancées, voir le manuel complet. CONFORMITÉ Un guide complet de la conformité du produit est disponible dans le manuel du produit AC30V. Avertissement –...
L’utente deve analizzare tutti gli aspetti dell’applicazione, seguendo le normative industriali applicabili e tenere in considerazione le informazioni riguardanti il prodotto contenute in questo opuscolo e in ogni altro materiale fornito da Parker, società affiliate e distributori autorizzati.
Seite 27
Italiano ATTENZIONE! - Ignorare le seguenti regole potrebbe causare incidenti o danneggiare il convertitore SICUREZZA In caso di discordanza le norme di sicurezza del personale hanno la precedenza nei confronti delle norme EMC cablaggi siano dimensionati per la maggiore delle Non effettuare test di resistenza ad alto tensione tensioni utilizzate nel sistema.
Italiano GUIDA RAPIDA PRIMA DI INIZIARE Questo documento descrive i passaggi fondamentali per mettere in funzione l’inverter AC10. La messa in funzione di un inverter deve essere affidata ad elettricisti qualificati, che conoscano gli inverter AC e le relative applicazioni. Per maggiori informazioni su installazione, sicurezza ed applicazioni consultare il Manuale del prodotto AC10.
Seite 29
Italiano Codice prodotto – Vedere pagina 1-4 Gamma di prodotti – Vedere pagina 1-5 Messa in funzione dell’inverter Leggere la sezione Sicurezza nella prima pagina della guida rapida. Accertarsi che tutte le norme elettrotecniche locali siano rispettate. Controllare l’eventuale presenza di danni.
Seite 30
Italiano Collegamenti di base 0.2kW – 22kW Basic Wiring Diagram for Multi-stage speed control macro (NPN type) 30kW – 180kW Basic Wiring Diagram for Three-phase AC drives (NPN type) 30kW – 180kW Basic Wiring Diagram for Three-phase AC drives (NPN type)
Seite 31
Italiano Keypad LED indica frequenza di marcia, frequenza infiammante bersaglio, codice funzione, il valore del parametro o il codice di errore. 4 LED indicano lo stato di lavoro. RUN durante l'esecuzione. FWD correre avanti e FRQ quando la MMI sta mostrando frequenza. Premere il tasto "M"...
Seite 32
Italiano Impostare i limiti F111 Max Frequency (Hz) Setting range: F113~650.0 Mfr’s value: 50.00 F112 Min Frequency (Hz) Setting range: 0.00~F113 Mfr’s value: 0.50 Impostare la velocità di rampa F114 First Acceleration Time (S) Mfr’s value: subject to F115 First Deceleration Time (S) Setting range: inverter model...
Italiano CONFORMITÀ Nel manuale del prodotto AC30V è disponibile una guida completa alla conformità del prodotto. Attenzione – In caso di conflitto tra i requisiti EMC e di sicurezza, la sicurezza del personale deve sempre prevalere. L’uso di questa apparecchiatura richiede istruzioni dettagliate di installazione e funzionamento, fornite nel manuale del prodotto.
Parker lub jej podmioty zależne bądź autoryzowanych dystrybutorów. W odniesieniu do opcji komponentów lub systemu dostarczanych przez firmę Parker lub jej spółki zależne lub autoryzowanych dystrybutorów na podstawie danych lub specyfikacji dostarczonych przez użytkownika, użytkownik jest odpowiedzialny za zapewnienie, że takie dane i specyfikacje są...
Polsk NIEBEZPIECZEŃSTWO! – zignorowanie poniższych informacji może skutkować powstaniem obrażeń ciała lub uszkodzeniem urządzenia BEZPIECZE STWO W przypadku wykluczających się wymogów dotyczących kompatybilności EMC i bezpieczeństwa, pierwszeństwo mają zawsze wymogi dotyczące bezpieczeństwa personelu. Przed wykonywaniem pomiaru rezystancji izolacji na W przypadku wymiany napędu konieczne jest przed okablowaniu wysokiego napięcia należy zawsze ponownym rozpoczęciem użytkowania prawidłowe...
Polski INSTRUKCJA SZYBKIEGO URUCHOMIENIA PRZED ROZPOCZĘCIEM Niniejszy dokument opisuje czynności niezbędne do pierwszego uruchomienia przemiennika serii AC10. Pierwsze uruchomienie przemiennika powinno być wykonywane przez kompetentnych techników elektryków, którzy są zaznajomieni z przemiennikami prądu zmiennego oraz ich zastosowaniem. Szczegółowe informacje na temat montażu, bezpieczeństwa i zastosowań znajdują się w Instrukcji produktu AC10. Upewnić...
Seite 37
Polsk Produkcie Code – Patrz strona 1-4 gama produktów – Patrz strona 1-5 Uruchomienie przemiennika Przeczytać informacje dotyczące bezpieczeństwa umieszczone przed instrukcją szybkiego uruchomienia. Upewnić się, że montaż przemiennika jest zgodny ze wszystkimi lokalnymi przepisami elektrycznymi. Sprawdzić, czy urządzenie nie jest uszkodzone. ...
Seite 38
Polski Podstawowe połączenia 0.2kW – 22kW Basic Wiring Diagram for Multi-stage speed control macro (NPN type) 30kW – 180kW Basic Wiring Diagram for Three-phase AC drives (NPN type)
Seite 39
Polsk Keypad Pokazy LED działa częstotliwość, migające częstotliwości docelowej, kod funkcji, wartość parametru lub kod błędu. 4 diody LED sygnalizujące stan pracy. RUN podczas jazdy. FWD działa do przodu i FRQ gdy MMI pokazuje częstotliwość. Naciśnij "M" dla kodu funkcji, a "E" do oryginalnych parametrów.
Seite 40
Polski Ustaw limity F111 Max Frequency (Hz) Setting range: F113~650.0 Mfr’s value: 50.00 F112 Min Frequency (Hz) Setting range: 0.00~F113 Mfr’s value: 0.50 Ustaw ramp F114 First Acceleration Time (S) Mfr’s value: subject F115 First Deceleration Time (S) Setting range: inverter model 0.1~3000...
Polsk KOMPATYBILNOŚĆ Szczegółowe wytyczne dotyczące zapewnienia kompatybilności produktu są podane w Instrukcji produktu AC30V. Niebezpieczeństwo - w przypadku wykluczających się wymogów dotyczących kompatybilności EMC i bezpieczeństwa, pierwszeństwo mają zawsze wymogi dotyczące bezpieczeństwa personelu. Praca z niniejszym urządzeniem wymaga dokładnych instrukcji montażu i obsługi podanych w instrukcji przewidzianej do stosowania z niniejszym produktem.
Parker o sus filiales o distribuidores autorizados. En la medida en que Parker o sus filiales o distribuidores asociados proporcionen opciones de componentes o sistemas basándose en datos o especificaciones proporcionadas por el usuario, el usuario es responsable de determinar que dichos datos o especificaciones sean adecuados y suficientes para todas las aplicaciones y los usos previsibles razonables de los componentes o sistemas.
Seite 43
Español Para mediciones utilice solamente un medidor que cumpla con IEC 61010 (CAT III o superior). Comience siempre utilizando el rango más alto. Los medidores que cumplen con CAT I y CAT II no se deben utilizar en este producto. ADVERTENCIA - Ignorar lo siguiente puede resultar en lesiones o daños al equipo SEGURIDAD Cuando exista un conflicto entre EMC y los requerimientos de seguridad, la...
Español INICIO RÁPIDO ANTES DE COMENZAR En este documento se tratan los pasos necesarios para la puesta en funcionamiento básica de la unidad AC10. Las puestas en funcionamiento de la unidad deben ser llevadas a cabo por técnicos en electricidad competentes que estén familiarizados con las unidades AC y sus aplicaciones.
Seite 45
Español Código producto - Vedere pagina1-4 Gamma di prodotti - Vedere pagina 1-5 Puesta en marcha de la unidad Lea la sección Seguridad que se encuentra en la parte frontal del manual de inicio rápido. Asegúrese de cumplir con todos los códigos eléctricos locales. ...
Seite 46
Español Conexiones básicas 0.2kW – 22kW Basic Wiring Diagram for Multi-stage speed control macro (NPN type) 30kW – 180kW Basic Wiring Diagram for Three-phase AC drives (NPN type)
Seite 47
Español LED muestra corriendo frecuencia, intermitente frecuencia Keypad objetivo, el código de la función, el valor de parámetro o el código de fallo. 4 LEDs indican el estado de trabajo. RUN mientras se ejecuta. FWD corriendo hacia adelante y FRQ cuando el MMI está mostrando la frecuencia.
Seite 48
Español Establecer los límites F111 Max Frequency (Hz) Setting range: F113~650.0 Mfr’s value: 50.00 F112 Min Frequency (Hz) Setting range: 0.00~F113 Mfr’s value: 0.50 Establecer las tarifas de rampa F114 First Acceleration Time (S) Mfr’s value: subject to F115 First Deceleration Time (S) Setting range: inverter model...
Español CUMPLIMIENTO En el manual del producto AC30V se encuentra disponible una guía completa acerca del cumplimiento del producto. Advertencia: cuando exista un conflicto entre EMC y los requisitos de seguridad, la seguridad del personal tendrá prioridad en todo momento. Para poder utilizar este equipo, es necesario disponer de instrucciones detalladas acerca de la instalación y el funcionamiento que se proporcionan en el manual del producto destinado a utilizarse con este producto.
Användaren måste analysera alla aspekter av tillämpningen samt följa såväl tillämpbara branschnormer som produktinfor- mation i aktuell produktkatalog och i annat material som Parker, dess dotterbolag eller godkända distributörer tillhandahåller. Såvida Parker, dess dotterbolag, eller auktoriserade distributörer tillhandahåller komponent- eller systemalternativ baserade på...
Seite 51
Svenska VARNING! - Om du inte beaktar följande kan det orsaka personskador eller skador på utrustningen SÄKERHET Om det finns en konflikt mellan EMC- och säkerhetskraven ska den personliga säkerheten alltid prioriteras. Kontrollera aldrig högspänningsmotståndet När du byter ut en enhet i en tillämpning och innan i kablaget utan att först koppla bort enheten den tas i bruk igen måste alla användardefinierade från den krets som testas.
Svenska SNABBSTART INNAN DU STARTAR I det här dokumentet beskrivs de steg som ingår i en normal start av AC10-enheten. Enheten ska startas av en kvalificerad eltekniker som behärskar frekvensomoriktare och hur de kan användas. Detaljerad information om installation, säkerhet och tillämpningar finns i produkthandboken för AC10. Se till att alla lokala elnormer uppfylls under installationen.
Seite 53
Svenska Produktkod – se sidan 1-4 Sortiment - se sidan 1.5 Starta enheten Läs avsnittet om säkerhet i början av Snabbstarten. Se till att alla lokala elektriska normer följs. Kontrollera att utrustningen inte är skadad. Sök efter lösa kabeländar, filspån, rester från borrning etc. i enheten och systemet. ...
Seite 54
Svenska Grundläggande anslutningar 0.2kW – 22kW Basic Wiring Diagram for Multi-stage speed control macro (NPN type) 30kW – 180kW Basic Wiring Diagram for Three-phase AC drives (NPN type)
Seite 55
Svenska Keypad LED visar kör frekvens, blinkande målfrekvens, funktionskod, parametervärdet eller fel code. 4 lysdioder indikerar sysselsättningsstatus. KÖR medan du kör. FWD kör framåt och FRQ när MMI visar frekvensen. Tryck på "M" för kod för funktionen, och "E" för original parametrar.
Seite 56
Svenska Sätter gränserna F111 Max Frequency (Hz) Setting range: F113~650.0 Mfr’s value: 50.00 F112 Min Frequency (Hz) Setting range: 0.00~F113 Mfr’s value: 0.50 Ställ in ramp priser F114 First Acceleration Time (S) Setting Mfr’s value: subject F115 First Deceleration Time (S) inverter model range: F116 Second Acceleration Time (S)
Svenska INSTALLATIONSKRAV Heltäckande information om produktens installation finns i produktmanualen för AC30V. Varning! – Om det finns en konflikt mellan EMC- och säkerhetskraven ska den personliga säkerheten alltid prioriteras. För att kunna använda den här utrustningen krävs de detaljerade anvisningar om installation och drift som finns i produktmanualen.
中文 变频器认证 警告 –电磁兼容和安全要求之间如有冲突,以人员安全为重。 操作该设备需要阅读随机附带的详细的安装和操作指南说明。详细说明书包含在设备包装盒 内,可能是 CD,软盘或其他设备。说明书应该随时与设备放在一起。 注意:根据 IEC 61800-3,本产品属于限制性销售级别。根据 EN61000-3-2 定义,本产品设计为“专业设 备”。连接至低压电源前,须取得供电局许可。 在内部环境中,本产品会产生电磁干扰,用户可能需要采取相应的防范措施。 本设备装有静电放电(ESD)感应配件。操作,安装和维修时,注意观察静电控制预警装置。. EMC Emissions Radiated Emissions comply with EN61800-3 category C1, C2 and C3 when installed in accordance with instructions. Conducted Emissions comply with EN61800-3 category C3 external filter . Immunity complies with the requirement of EN61800-3, for equipment intended for use in the second environment.
Chapter 9 Dimensions for Installations Inverter should be installed vertically, Sufficient ventilation space should be ensured. Space between 2 drive 25mm. Clearance Dimensions Model Clearance Dimensions Plastic Hanging A≥150mm B≥50 mm Metal Hanging A≥200mm B≥100mm Instalation Dimensions External Dimension Max Weight Mounting Frame Mounting Bolt...