6.2
Pressure testing the inner pipe
WARNING
Risk of injury and/ or damage due to pressure testing!
Using hazardous media for pressure testing may put the installation at risk
and cause physical damage or bodily harm in case of leakage.
The pressure test must be performed using non-harzardous media (e.g
water) and with due care and attention in handling.
Please pay attention to the instructions in the user manual for
diaphragm valve type 514, 515, 517, 519.
Check to make sure the protective housing is open (cover removed) to determine
if there is leakage during the pressure testing.
The pressure test must be performed with water or another non-hazardous
medium. See DVS 2210-2 with reference to DVS 2210-1, Suppl. 2, as well as the
instructions contained in the above mentioned Installation and Instruction
Manual for Diaphragm Valve Type 514, 515, 517, 519.
When the pressure test has been successfully completed, proceed to
Assembling the CONTAIN-IT Plus Diaphragm Valve
42