Herunterladen Inhalt Inhalt Diese Seite drucken

Supply Air Fan Parameters (Visible If P05 = 1 Or 2 Or 3) - Carrier CCU Regelungshandbuch

Vorschau ausblenden Andere Handbücher für CCU:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 79
6 - CONFIGURING THE UNIT
6.2.3 - Alarm (sub-menu 9.3)
Alarm
Mn
EC
E1
E0
EH
EP
EU 
EF
ED 
To acknowledge a fault on the humidifier, go to the "ALARM" menu (menu 9.3) and press the "Reset" key

6.3 - Supply air fan parameters (visible if P05 = 1 or 2 or 3)

6.3.1 - FMA1 information (sub-menu 10.1)
Access level
No.
1
1000
1
1001
1
1002
1
1003
1
1004
1
1005
1
1010
1
1011
1
1012
1
1013
1
1014
1
1015
1
1020
1
1021
1
1022
1
1023
1
1048
1
1049
Description
The humidifier has no fault
Replace the cylinder
Water conductivity too high
Configuration parameter error
Internal memory error 
Electrode overcurrent 
Low steam flow rate during reduced production
Water level raised without humidification request
Lack of supply water
Drain problem 
Description
FMA1 max. speed
FMA1 requested speed
FMA1 current speed
FMA1 current consumed
FMA1 peak supply voltage
FMA1 power input
FMA1 fault summary
FMA1 start-up fault
FMA1 rotation direction fault
FMA1 current limitation
FMA1 temperature limitation
FMA1 off
FMA1 internal DC voltage
FMA1 IGBT temperature
FMA1 indoor room temperature
FMA1 MCU temperature
FMA1 product code
FMA1 software version
Unit
Display condition
rpm
P05 = 1, 2 or 3
rpm
P05 = 1, 2 or 3
rpm
P05 = 1, 2 or 3
A
P05 = 1, 2 or 3
V
P05 = 1, 2 or 3
W
P05 = 1, 2 or 3
Off/On
P05 = 1, 2 or 3
Off/On
P05 = 1, 2 or 3
Off/On
P05 = 1, 2 or 3
Off/On
P05 = 1, 2 or 3
Off/On
P05 = 1, 2 or 3
Off/On
P05 = 1, 2 or 3
V
P05 = 1, 2 or 3
°C 
P05 = 1, 2 or 3
°C
P05 = 1, 2 or 3
°C
P05 = 1, 2 or 3
P05 = 1, 2 or 3
P05 = 1, 2 or 3
61