6 - CONFIGURING THE UNIT
Access level
No.
Description
2
209
Low temperature (2 V)
2
210
High temperature (10 V)
Cooling temperature setpoint with 
2
211
2-10 V sensor fault
Heating temperature setpoint with
2
212
2-10 V sensor fault
2
215
Unit number on console
6.1.3 - Reading parameters (sub-menu 3.3)
This third sub-menu gives access to all the values (temperatures, relative humidities, pressures, time delays, meters, input and output 
states, etc.) managed by the CCU CONTROLLER.. Only the useful parameters are displayed. They cannot be modified 
The meters can be reset to zero. To do this, place the cursor on the chosen meter and simultaneously press the Reset and 0 keys for 
5 to 6 seconds.
All these parameters are accessible from the "customer" access level. 
Access level
No.
Description
1
250
Cooling setpoint value 
1
251
Temperature setpoint value in heating mode 
1
252
Air flow activation threshold value 
1
253
Filter fouling activation threshold value
1
254
Filter clogging activation threshold value
1
255
Target temperature
1
256
Target relative humidity
1
257
Filter differential pressure 
1
258
Outdoor temperature
1
259
Supply air temperature 
1
265
Outdoor humidity
1
266
Raised floor differential pressure
1
267
Fan 1 differential pressure
1
268
External weight in water
1
269
Air flow rate
1
270
Electric heater safety thermostat with manual reset
1
271
Summary of condensation unit 1 faults
1
272
Summary of condensation unit 2 faults
1
278
External safety contact
1
279
On request contact
1
281
Humidifier maintenance, fault or operation feedback
1
282
Fan operation feedback
1
284
Water leak contact
1
287
Hot water coil or electric heater selection contact
1
288
Summer or winter mode contact
58
Setting
CONTROLLED TEMPERATURE ORIGIN SELECTION
-40.0 to 99.9 °C
-40.0 to 99.9 °C
8.0 to 45.0 if P08 > 0
MAX (8,P212) to 45.0 °C if P07>0
MASTER/SLAVE BUS
1 to 32
CALCULATED SETPOINT
MEASURED VALUE
LOGIC INPUT STATE (ON/OFF)
By default Display condition
(P07 > 0 or P08 > 0) and P207 = 
-20.0 °C
2
(P07 > 0 or P08 > 0) and P207 = 
80.0 °C
2
25.0 °C
P07 > 0 and P207 = 2
20.0 °C
P08 > 0 and P207 = 2
1
Unit
Display condition
°C
P07 > 0
°C 
P08 > 0
Pa
P02 ≠ 17 
Pa
Pa
°C
P07 > 0 or P08 > 0
%
P09 > 0 or P10 > 0
Pa
°C
P11 = 1
°C
P06 = 1
(P09 > 0 or P10 > 0) and P11 = 
%
1
Pa
P2 = 16
Pa
P02 = 17
g/Kg
(P09>0 or P10>0) and P11=1
m³/h
P02 = 17
default = off
default = on P17 > 5
default = on P17 > 6
default = off P10 = 1
default = off
default = off
electric off
P08 = 3
hot water on
summer off
P19 = 1
winter on