6 - CONFIGURING THE UNIT
Access level
No.
Description
Free cooling activation 
2
125
differential
Free cooling activation low limit 
2
126
setpoint
2
128
Free cooling opening limit
External weight in water low 
2
129
limit setpoint
External weight in water high 
2
130
limit setpoint
1
140
Low limit setpoint 
Proportional band for the low 
1
141
limit
1
142
High limit setpoint
Proportional band for the high 
1
143
limit
2
144
Cooling setpoint offset
2
145
Heating setpoint offset
2
146
Air flow rate setpoint
2
147
Air flow rate proportional band
2
148
Air flow rate integration time 
2
149
Air flow rate derivation time
2
150
Discharge pressure setpoint 
Discharge pressure 
2
151
proportional band
Discharge pressure integral 
2
152
time
Discharge pressure derivative 
2
153
time
Electric heater maximum 
2
154
percentage
Percentage of the rotation 
2
155
speed
Minimum percentage of the
2
156
rotation speed
Maximum percentage of the 
2
157
rotation speed
Percentage of proportional 
2
158
bands reserved for controlling 
just the valves 
Return/supply air temperature 
2
159
differential setpoint
Return/supply air temperature 
2
160
proportional band
56
Setting
FREE COOLING CONTROL
3 to 20 K
-5 to 20°C
0 to 100%
0 to 15 g
8 to 18 g
LIMITATION OF THE SUPPLY AIR TEMPERATURE
5 to 30 °C
1 to 20 K
30 at 60°C
1 to 20 K 
TEMPERATURE SETPOINT SHIFT
0 to 30 K
0 to 20 K
AIR FLOW
4000 to P40 m³/h
100 to 50,000 m³/h
0 to 1800 s
0 to 1800 s
FLOOR PRESSURE
20 to 250 Pa
20 to 1000 Pa
0 min 0 s to 30 min 0 s (0 to 1800 s)
0 min 0 s to 30 min 0 s (0 to 1800 s)
LIMITING THE POWER OF THE GRADUAL ELECTRIC HEATER
0 to 100%
LIMITATION OF THE FAN ROTATION VARIABLE SPEED CONTROL
P156 to P157
0 to 90 % if P08 = 0 or 1 and P10 = 0
50 to 90% if P08 > 1 or P10 > 0
P156 to 100%
0 to 100%
RETURN/SUPPLY AIR TEMPERATURE CONTROL
5.0 to 20.0 °C
1.0 to 10.0 °C
By default
Display condition
3 K
P11 = 1
0°C
P11 = 1
100%
P11 = 1
P11 = 1 and 
4 g
(P09>0 or 
P10>0)
P11 = 1 and
12 g
(P09 >0 or 
P10 > 0)
P06 = 1 and (P07 > 0 or P09 > 
14°C 
0)
P06 = 1 and (P07 > 0 or P09 > 
4 K
0)
50°C
P06 = 1 and P08 > 0
4 K
P06 = 1 and P08 > 0
5 K
P31 > 0
5 K
P32 > 0
1000 m³/h
P02 = 17
6000 m³/h
P02 = 17
0 s
P02 = 17
0 s
P02 = 17
100 Pa
P2 = 15
50 Pa
P2 = 15
3 min 0 s
P2 = 15
3 min 0 s
P2 = 15
(P08 = 2 or 3) and (P16 = 3 or 
100%
4)
(P156+P157)/2
60%
P02 > 9
100%
P02 > 9
50 % 
P02 = 10 to 13
10.0 °C
P2 = 16
2.0 °C
P2 = 16