1 - GENERAL INFORMATION

The CCU CONTROLLER is fitted as standard to Close Control Unit systems. Setting and display console equipped with a 160-character 
LCD screen. The CCU CONTROLLER is equipped with a microprocessor and an expansion board to provide the following functions: 
■ Filtration
Checking the pressure drop in the filters, by monitoring the air flow and fouling level. 
■ Control function (Cooling Mode)
• Chilled water model:
Gradual opening of the three-way valve following an increase in temperature. 
• Direct expansion model:
Triggering of one or more refrigerating stages following an increase in temperature. (Action on condensation unit).
■ Control function (Heating Mode)
- Hot water coil model:
Gradual opening of the three-way valve following a decrease in temperature. 
- Electric heater model:
Triggering of one or two stages following a decrease in temperature. 
■ Control function (Dehumidification Mode)
- Opening of a chilled water valve or triggering of refrigerating stages, following an increase in humidity. 
- Triggering of heating mode if there is a drift in temperature.
- As an option, decrease in the air flow to increase the latent part of the cooling capacity. 
■ Control function (Humidification Mode)
- Triggering of humidification following a decrease in humidity. 
■ Fan control
- Management of operation and faults for a 1-speed fan or variable-speed control fan. 
- Fan on/off via an outer contact, internal timer. 
- Variable speed control via temperature or humidity control, or raised floor pressure, or for constant flow control.
- Time-limited post ventilation for an electric heater. 
- Interlock the controls and controllers to operation of the fan. 
- Shift in start-up if there are several units at the same site. 
- Soft start of the ventilation if there is a variable air volume.
■ Safety and alarms
- Overheating thermostat (Manual reset) on the electric heater. 
- Pressure sensor for checking the air flow and filter fouling (Thresholds interlocked to the variation in the air flow).
- Configurable alarm threshold for high and low temperature. 
- Configurable alarm threshold for high and low humidity. 
- Low supply air temperature limitation sensor (limitation of the cooling capacity). 
- Water leak control.
■ Configurable potential-free (dry) contacts made available for:
- Critical fault summary: air flow, fan, compressors, clogged filter, temperature sensor.
- Non-critical  fault  summary:  filter  fouled,  electric  heater,  humidifier,  water  leak,  target  temperatures  exceeded,  target  relative 
humidity exceeded.
■ Memorisation
- Memorisation of the last 20 faults with the date and time of each fault, plus the readings of all the analogue input values at the 
time of the fault. 
- Parameter setting memorisation in the event of a power failure.
■ Remote control
- Option of remote control.
■ Metering
- Option to display metering for: 
- The number of operating hours for the fans, compressors, electric heater stages, the humidifier, the fault summaries sent with 
individual reset of each meter. 
- The number of compressor start-ups.
42