6 - CONFIGURING THE UNIT
Access level
No.
Description
2
99
Locking of the configuration
(*) When these parameters are modified, a sequence is launched to configure the FMAs.
6.1.2 - CONTROL AND SETTINGS (sub-menu 3.2)
Access level
No.
Description
1
100
Language used
1
101
Date
1
102
Time
Temperature setpoint in cooling 
1
103
mode
Temperature proportional band 
1
104
in cooling mode
Temperature integral time in 
1
105
cooling mode
Temperature setpoint in heating
1
106
mode
Temperature proportional band 
1
107
in heating mode
Integral time Temperature in 
1
108
heating mode
Humidity setpoint during 
1
109
dehumidification
Humidity proportional band in 
1
110
dehumidification mode
Humidity integral time in 
1
111
dehumidification mode
Humidity setpoint during 
1
115
humidification
Humidity proportional band in 
1
116
humidification mode
Humidity integral time in 
1
117
humidification mode
Downward shift of the 
1
121
temperature limit
Proportional band for reduction 
1
122
of the cooling demand
Setting
LOCKING
0: Configuration unlocked 
(The unit cannot be started up; the unit type 
parameters may be changed).
1: Configuration locked 
(The unit can be started up by pressing the 
"On/Off" push button on the console. The 
unit  type  parameters  may  no  longer  be 
modified.  The  number  of  times  the 
configuration is unlocked is counted.)
Setting
0: French
1: English
2: German
3: Spanish
Day/Month/Year
Hours/Minutes
COOLING CONTROL
8.0 to 45.0 °C if P08 = 0
MAX (10, P106) to 45.0 °C if P08 > 0
1.0 to 10.0 K
0 min 0 s to 30 min 0 s (0 to 1800 s)
HEATING CONTROL
10.0 to 35.0 °C
10.0 to MIN (35.0, P103) °C
1.0 to 10.0 K
0 min 0 s to 30 min 0 s (0 to 1800 s)
DEHUMIDIFICATION CONTROL
20 to 90% if P10 = 0
MAX (20, P115) to 90 % if P10 > 0
5 to 30%
0 min 0 s to 30 min 0 s (0 to 1800 s)
HUMIDIFICATION CONTROL
20 to 90% if P09 = 0
MAX (20, P109) to 90 % if P09 > 0
5 to 30%
0 min 0 s to 30 min 0 s (0 to 1800 s)
RETURN TEMPERATURE LIMITATION
0.0 to 10.0 K
1.0 to 10 K
By default Display condition
0
By default Display condition
0
25.0 °C
P07 > 0
2.0 K
P07 > 0
0 min 0 s P07 > 0
20.0 °C
P08 > 0
2.0 K
P08 > 0
0 min 0 s P08 > 0
60%
P09 > 0
10%
P09 > 0
0 min 0 s P09 > 0
40%
P10 > 0
10%
P10 > 0
0 min 0 s P10 > 0
2 K
P06 = 0 and P09 > 0
2 K
P06 = 0 and P09 > 0
55